THIS IS A HEATING APPLIANCE

DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANELS INSTALLED.

•  Due  to  high  temperatures,  the  appliance  should  be 

located  out  of  traffic  and  away  from  furniture  and 

draperies.

•  Children and adults should be alerted to the hazards 

of high surface temperatures and should stay away to 

avoid burns or clothing ignition.

•  Young children should be carefully supervised when 

they are in the same room as the appliance.

•  Clothing  or  other  flammable  material  should  not  be 

placed on or near the appliance.

•  Any  safety  screen  or  guard  removed  for  servicing 

an appliance must be replaced prior to operating the 

appliance.

•  Keep burner and control compartment clean.

• 

Installation and repair should be done by a QUALIFIED 

SERVICE PERSON. The appliance should be inspected 

before use and at least annually by a qualified service 

person. More frequent cleaning may be required due 

to excessive lint from carpeting, bedding materials, 

etc. It is imperative that control compartments, burners 

and circulating air passageways of the appliance be 

kept clean.

•  Do  NOT  put  anything  around  the  furnace  that  will 

obstruct the flow of combustion and ventilation air.

•  DO  keep  the  appliance  area  clear  and  free  from 

combustible material, gasoline and other flammable 

vapors and liquids.

•  DO examine venting system periodically and replace 

damaged parts.

•  DO make a periodic visual check of pilot and burners. 

Clean and replace damaged parts.

•  CAUTION: Pilot hole cover must be kept tightly closed 

during operation.

•  DO NOT use this heater if any part has been under 

water. Immediately call a qualified service technician 

to inspect the heater and to replace any part of the 

control system and any gas control which has been 

under water.

•  This furnace must not be connected to a chimney flue 

serving a separate soid-fuel burning appliance.

When an existing Category 1 heater is removed or replaced, the 

original venting system may no longer be sized to properly vent the 

attached appliances. Instructions shall also indicate effects of an 

improperly sized venting system (formation of condensate, leakage, 

spillage, etc.) and shall specify the following test procedure:

 

 WARNING

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  the  steps  outlined  below  for  each 

appliance  connected  to  the  venting  system  being  placed 

into operation could result in carbon monoxide poisoning 

or death.

The  following  steps  shall  be  followed  for  each  appliance 

connected  to  the  venting  system  being  placed  into 

operation,  while  all  other  appliances  connected  to  the 

venting system are not in operation:

1. 

Seal any unused openings in the venting system.

2. 

Inspect  the  venting  system  for  proper  size  and 

horizontal pitch, as required in the National Fuel Gas 

Code, ANSI Z223.1/NFPA 54 or the Natural Gas and 

Propane  Installation  Code,  CSA  B149.1  and  these 

instructions.  Determine  that  there  is  no  blockage  or 

restriction,  leakage,  corrosion  and  other  deficiencies 

which could cause an unsafe condition.

3. 

As  far  as  practical,  close  all  building  doors  and 

windows  and  all  doors  between  the  space  in  which 

the appliance(s) connected to the venting system are 

located and other spaces of the building.

4. 

Close fireplace dampers.

5. 

Turn on clothes dryers and any appliance not connected 

to the venting system. Turn on any exhaust fans, such 

as  range  hoods  and  bathroom  exhausts,  so  they  are 

operating  at  maximum  speed.  Do  operate  a  summer 

exhaust fan.

6. 

Follow  the  lighting  instructions.  Place  the  appliance 

being  inspected  into  operation.  Adjust  the  thermostat 

so appliance is operating continuously.

7. 

Test for spillage from draft hood equipped appliances 

at the draft hood relief opening after 5 minutes of main 

burner operation. Use the flame of a match or candle.

8. 

If  improper  venting  is  observed  during  any  of  the 

above tests, the venting system must be corrected in 

accordance with National Fuel Gas Code, ANSI Z223.1/

NFPA 54 and/or Natural Gas and Propane Installation 

Code, CSA B149.1.

9.  After  is  has  been  determined  that  each  appliance 

connected 

to the venting system properly vents when 

tested  as  outlined  above,  return  doors,  windows, 

exhaust fans, fireplace dampers and any other gas-fired 

burning appliance to their previous conditions of use.

Summary of Contents for FAW55SPPXLP-1

Page 1: ...ately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If not installed operated and maintained in accordance with the manufacturer s instructions this product could expose you to substance...

Page 2: ...nclosure 36 914mm for rooms up to 118 1 2 301cm in height DV648DBD 4 102mm Oval to Round flue adapter kit CONVERSION KITS Part Number Description Used On 682161 Propane to Natural FAW55SPPXLP 1 682270 Natural to Propane FAW55SPPXNAT 1 Important All correspondence should refer to complete Model No Serial No and type of gas NOTICE During initial firing of this unit its paint will bake out and smoke ...

Page 3: ...o indicate effects of an improperly sized venting system formation of condensate leakage spillage etc and shall specify the following test procedure WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death The following steps shall be followed...

Page 4: ...s can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity Propane Gas may stratify in a closed area and the odor intensity could vary at different levels Since it is heavier than air there may be more odor at lower levels Always be sensitive to the slightest gas odor If you detect any od...

Page 5: ... of 10 feet 3m 2 This furnace must not be connected to a chimney flue serving a separate solid fuel burning appliance 3 Uninsulated Single Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 Attention ThisFanTypeVentedWallFurnaceisequippedwith a vent safety switch In the event of spillage of flue products due to improper venting the vent safety switc...

Page 6: ...on center studs will not allow the furnace to be recessed into the wall unless a stud is repositioned A template is proved in furnace carton for locating gas line connec tion Also refer to Figure 2 for positioning the furnace on wall and for locating gas line connection Locating Gas Supply The gas line can enter the furnace either though the floor or wall The gas line opening should be made at thi...

Page 7: ...e gas line it is suggested that a match be used The match will light the pilot faster than the piezo under this condition Attention The 7 8 22mm strain relief bushing is located within the same yellow envelope as the Installation Instructions and Owner s Manual Attaching Furnace to Wall Whenattachingfurnacetothewallremovethatportionofbaseboard and molding on the wall which is behind the furnace At...

Page 8: ...it passes through combustibles 10 3m OR LESS 3 9m MIN 2 6m MIN Figure 8 Proper Pilot Flame The correct pilot flame Figure 6 will be blue extending past the thermocouple The flame will surround the thermocouple just be low the tip Natural Gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remove the pilot cover screw on the control valve Figure 5 and turn the adjustmen...

Page 9: ...s available in the supply tubing the pilot orifice and or pilot burner is probably restricted by a spider web Clean pilot assembly and relight If Pilot Does Not Remain On After Releasing Knob 1 Follow instructions and hold button down longer and harder 2 Determine if pilot flame extends past thermocouple if not adjust input or clean pilot burner 3 Replace thermocouple if millivolts read less than ...

Page 10: ...STOP Read safety information above 2 Turn off all electric power to the appliance 3 Remove control access panel lower front panel 4 Turn gas control knob clockwise to OFF GAS CONTROL KNOB SHOWN IN OFF POSITION 5 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next st...

Page 11: ... first floor ceiling and one pair of fire stop spacers at each successive ceiling level C 4 102mm Oval In The Wall wall parts purchase locally 1 Type B 1 oval pipe 2 Type B 1 oval elbows 3 Single story type B 1 gas vents require a baseplate and one pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the first floor ceiling and one...

Page 12: ...808 PILOT TUBING W FERRULES 25 DV562 LOWER FRONT PANEL 26 DV824 FRONT BURNER 27 P8842 MAIN BURNER ORIFICE NATURAL GAS TWO REQUIRED 27 P8853 MAIN BURNER ORIFICE PROPANE GAS TWO REQUIRED 28 DV687 MANIFOLD AND PLATE ASSEMBLY 29 M148 MANIFOLD GASKET 30 DV064 COVER PLATE FOR OBSERVATION HOLE 31 DV847 BURNER DOOR NATURAL GAS 31 DV973 BURNER DOOR PROPANE GAS 32 DV775 SEAL BRACKET 33 M147 GASKET TUBING SE...

Page 13: ...37406 5 0320 Page 13 ...

Page 14: ...ase and can be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the fol lowing illustration and part list Be ...

Page 15: ...ale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts to and from the factory Claims that do not involve defective workmanship or mat...

Page 16: ...www empirecomfort com Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer ...

Page 17: ...e maison voisine Suivre les instructions du fournisseur de gaz S il est impossible de joindre le fournisseur de gaz appeler le service d incendie L installation et l entretien doivent être exécutés par un installateur qualifié une agence de service ou par le fournisseur de gaz INSTALLATEUR Laissez cette notice avec l appareil CONSOMMATEUR Conservez cette notice pour consultation ultériure AVERTISS...

Page 18: ...ie arrière extension maximale de 10 po 254 mm registre réglable DV 651DB Boîtier d évent 356 mm 14 po pour les pièces jusqu à 96 1 2 po 245 cm de hauteur DV 665DB Boîtier d évent 610 mm 24 po pour les pièces jusqu à 270 5 cm 106 1 2 de hauteur DV 666DB Boîtier de ventilation 914 mm 36 po pour les pièces d une hauteur maximale de 301 cm 118 1 2 po DV648DBD Kit adaptateur de fumée de 4 po 102 mm ova...

Page 19: ...nt indiquer les effets d un système de ventilation de taille inadéquate formation de condensat fuite déversement etc et doivent spécifier la procédure d essai suivante AVERTISSEMENT DANGER D EMPOISONNEMENT AU MONOXYDE DE CAR BONE Le fait de ne pas suivre les étapes décrites ci dessous pour chaque appareil raccordé au système d évacuation mis en service pour rait entraîner un empoisonnement au mono...

Page 20: ...de gaz peut être adsorbée ou absorbée sur ou dans les murs maçonnerie et d autres matériaux et tissus dans une chambre Ceci enlèvera une quantité de l odeur du gaz affaiblissant l intensité de la senteur Le propane peut stratifier dans un endroit fermé et l intensité de l odeur peut varier à différents niveaux Puisque le propane est plus pesant que l air l odeur peut être plus prononcée à un bas n...

Page 21: ...et de Combustion Les radiateurs muraux doivent être installés dans un endroit où la facilité delaventilationpermetunecombustiondegazsatisfaisanteetunéchappe ment convenable sous des conditions normales Dans les bâtiments de construction conventionnelle de brique ou de pierre sans fenêtre et porte étanche l infiltration est normalement adéquate pour fournir l air pour la combustion et la dilution d...

Page 22: ...sur un mur Le radiateur a une largeur de 16 406mm et étant donné que la distance normale entre les montants du mur est de 16 406mm le radiateur pourra être encastré seulement si un montant est changé de place Un guide est fourni dans l emballage du radiateur pour vous aider à local iser la connexion pour la ligne de gaz Aussi référer à la Figure 2 pour positionner le radiateur sur le mur et pour l...

Page 23: ...ues Enlever l assemblage de la fichede3 914mm ducompartimentdescontrôles aubas duradiateur 2 Enlever l entrée défonçable de 7 8 22mm du côté du panneau ap proprié 3 Introduirelebouchondenylondel assemblagedelafichede3 914mm dans l ouverture de 7 8 22mm sur le côté du panneau 4 Brancherlebouchondenylondel assemblagedelafichede3 914mm à la fiche de nylon sur le harnais de fils électriques 5 Placer l...

Page 24: ... brûleur débrancher l alimentation de gaz à la valve et enlever les huit vis qui tiennent la porte du brûleur Après avoir enlevé la porte du brûleur de la chambre de combustion enlever le brûleur arrière le brûleur de la veilleuse et le brûleur de devant Avec les brûleurs de devant et arrière enlevés faire entrer de l eau avec force dans la bande d ouvertures et sécher avec une pression d air ET F...

Page 25: ... l évent avec une remise à zéro manuelle est situé sur le coupe tirage 3 Replacer le panneau de devant en haut Si l interrupteur de sûreté de l évent avec remise à zéro manuelle continu d arrêter le débit de gaz aux brûleurs principaux un technicien d entretien qualifié doit être contacté pour vérifier s il y a une évacuation inadéquate une obstruction dans le tuyau d échappement ou si l interrupt...

Page 26: ...ompris près du plancher pour déceler une odeur de gaz Si vous sentez le gaz ARRÊTER Suivre B dans les informations de sécurité ci dessus Si vous ne sentez aucun gaz aller à la prochaine étape 6 Enlever le couvercle d accès à la veilleuse situé sur la chambre de combustion 7 Trouverlaveilleuse suivreletuyau demétalàpartirducontrôledegaz La veilleuse est située entre les deux tuyaux des brûleurs der...

Page 27: ...umette 2 Utiliser le piezo allumeur à 30 secondes d intervalles jusqu à ce qu elle s allume Si l Électrode ne Produit Pas d Étincelle 1 Vérifier les connexions des fils électriques 2 Vérifier la distance du brûleur de la veilleuse au bout de l électrode Doit être entre 1 8 3mm et 3 16 5mm Le fil de l électrode et le bout doivent être éloignés à plus de 1 4 6mm de toutes autres pièces métalliques E...

Page 28: ...6 Bâti du ventilateur 10 11759 Panneau du côté 11 DV627 Panneau de devant en haut 12 R1619 Manchon 13 DV823 Assemblage du coupetirage 14 R1749 Interrupteur de sûreté de l évent 15 R1587 Assemblage des fils pour la sûreté de l évent 16 R1536 Manchon 17 11765 Assemblage du compartiment d interrupteur 18 DV832 Couvercle du compartiment d interrupteur 19 R630 Contrôle de tolérance 20 R1941 Contrôle du...

Page 29: ...37406 5 0320 Page 13 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529 ...

Page 30: ...a plaque du plafond 4 Les évents à gaz de type B 1 pour plus d un étage exige une plaque de base une paire d entretoises pour la plaque du pla fond au plafond du premier étage et une paire d entretoises pour l arrêt de feu à chaque niveau de plafond successif L espace entre les montants autour des évents à gaz doit être sans obstruc tion et sans papier de construction ACCESSOIRES Numéro pièce Desc...

Page 31: ... paiement pour attester de la date d achat et établir la période de garantie Accès immédiat à l appareil pour la réparation Ce qui n est pas couvert Dommages pouvant résulter de l emploi de l emploi abusif ou d une installation incorrecte de cet appareil Frais de déplacement de diagnostic et de transport des pièces sous garantie vers et depuis l usine Réclamations qui n impliquent pas des défauts ...

Page 32: ... Empire Comfort Systems Inc Belleville Illinois Pour toute question générale concernant nos produits veuillez nous envoyer un courriel à info empirecomfort com Pour toute question d entretien ou de réparation veuillez contacter votre revendeur ...

Reviews: