background image

19563-3-0907

Page 13

The appliance, when installed, must be electrically grounded in accordance 
with  local  codes  or,  in  the  absence  of  local  codes,  with  the  National 
Electrical Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA C22.1, 
if an external electrical source is utilized.  

This appliance is equipped 

with a three-prong [grounding] plug for your protection against shock 
hazard  and  should  be  plugged  directly  into  a  properly  grounded 
three-prong receptacle.  Do not cut or remove the grounding prong 
from this plug.  

For an ungrounded receptacle, an adapter, which has 

two prongs and a wire for grounding, can be purchased, plugged into the 
ungrounded receptacle and its wire connected to the receptacle mounting 
screw.  With this wire completing the ground, the appliance cord plug can 
be plugged into the adapter and be electrically grounded.  

CAUTION: 

 Label all wires prior to disconnection when servicing 

controls.  Wiring errors can cause improper and dangerous operation.  
Verify proper operation after servicing.  

Note:  For testing flame sensor circuit use a micro-amp meter in series 
with sensor.  Minimum current should be 1 micro-amp during operation.  
Be careful as flame sensor is in the 115VAC circuit.  If current is below 1 
micro-amp, remove sensor, clean with light sandpaper and retest. 

Note: This heater is equipped with a remote bulb electronic thermistor 
control located down low at the back of the furnace. Sometimes due to 
field locations different air currents may effect the control sensing of the 

thermistor. This sensing bulb can be re-located if necessary to provided 
for better room air sensing and control. 

Replacement of Thermistor with 24 Volt Wall Thermostat

 

1.  If furnace is installed, turn off gas supply and electric supply.

 

2.  Remove casing front.

 

3.  Remove black hose from front nipple on pressure switch.

 

4.  Remove junction box cover (4 screws).

 

5.  Please  refer  to  wiring  diagram  for  removal  of  the  following 

wires.

 

6.  Internal Electronic Thermostat/Temperature Control Board

Attention!  No 24 volt wall thermostat wires are to be attached 

to the internal electronic thermostat.

 

7.  Control Board

A.  Remove white wire form screw marked W.
B.  Remove yellow wire from screw marked C.
C.  Remove red wire from screw marked R.

 

8.  Route  (2)  wires  from  any  24  volt  wall  thermostat  through  the 

casing  back  of  furnace  to  the  screws  marked  W  and  R  on  the 
control board.

 

9.  Replace junction box cover (4 screws).

  10.  Replace black hose onto front nipple on pressure switch.
  11.  Replacement  of  thermistor  with  24  volt  wall  thermostat  is 

completed.

   

 

           

        

      

   

 

 

  

$% #

 #

 

 

 

 !"

##

 

$% #

 #

 

      && &&   &&         

 

'

!

"

 

 

$

 

 

#

$%

#

#

     

(

 

  

  

 

  

  

 

 

 

 

 

 

  

  

  

)   

 

)    

 )  

( )  

  #

 )   

# )  ##

 )  

%

$

%

WIRING

 ACF Greenhouses 

Summary of Contents for DV-55E

Page 1: ...his appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance Consumer Retain this...

Page 2: ...assachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 11 Lighting Instructions 12 Wiring 13 Maintenance 14 Operation and Trouble...

Page 3: ...nstallation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected beforeuseandatleastannuallybyaqualifiedserviceperson More frequent cleaning may be required due to...

Page 4: ...ights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption...

Page 5: ...naccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshall be permanently mounted to the exterior o...

Page 6: ...be performed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a th...

Page 7: ...ontrol valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the g...

Page 8: ...ning Conversion must be done by a qualified service technician Main burner orifice s and new gas conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to fur...

Page 9: ...NG The nearest point of the vent cap should be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce t...

Page 10: ...if plastic anchors are used Attach the two wall mounting brackets to the casing back by using 4 10 x 1 2 13mm hex head screws provided Figure 5 Figure 6 Figure 7 Figure 8 2 51mm TO 13 330mm 2 51mm TO...

Page 11: ...ach the right shroud and left shroud to the casing back the 3 4 wide flange on the shroud must be positioned toward the casing side When positioned correctly the 6 louvers on the shroud will be facing...

Page 12: ...lified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the therm...

Page 13: ...VAC circuit If current is below 1 micro amp remove sensor clean with light sandpaper and retest Note This heater is equipped with a remote bulb electronic thermistor control located down low at the ba...

Page 14: ...lve 4 Remove gas valve from gas valve bracket Removing Main Burner Orifice s 1 Remove front grill assembly 2 Remove burner compartment access panel 2 screws 3 Disconnect manifold union assembly 4 Disc...

Page 15: ...terminal on the board The inducer blower circuit is energized and the inducer blower comes on for 15 seconds pre purging out any gas and closing the pressure switch The hot surface ignitor is energize...

Page 16: ...essure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far from Burner...

Page 17: ...e Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of Gas...

Page 18: ...19563 3 0907 Page 18 PARTS VIEW ACF Greenhouses...

Page 19: ...19563 3 0907 Page 19 SERVICE NOTES ACF Greenhouses...

Page 20: ...3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com ACF Greenh...

Reviews: