Your  new  furnace  should  provide  many  years  of  trouble  free 
performance,  however,  a  yearly  inspection  of  the  burners  ,  flue 
passageways  and  the  outlet  vent  assembly  should  be  done.    Be 
sure all passageways are open and clear of any obstruction, or soot 
build up.  Be sure to shut off all power to the unit while performing 
this inspection.  

Periodically remove the circulating air filter and clean with water 
to remove all dirt.  Shake dry and reinstall in unit.

System Operation

1.  This  furnace  has  an  electronic  thermostat  and  control  board 

to monitor the room temperature and then control the furnace 
operation to provide the best comfort and performance from a 
heating appliance.  To operate unit turn ON/OFF switch to ON 
and then turn temperature control knob clockwise slowly till 
furnace turns on.  For typical room comfort, the control knob 
should be pointed toward medium.

2.  The furnace control board follows sequence of operation which 

allows for self diagnosis in the event there is a problem.  The 
control then blinks a status light, a set number of blinks based 
on what problem has been encountered.  When the furnace is 
on and there is a no fault condition, the red LED is on.

 

On a typical call for heat by the integral thermostat 24 VAC is 
applied to the W terminal on the board.   

 

The inducer blower circuit is energized and the inducer blower 
comes on for 15 seconds pre-purging out any gas and closing 
the pressure switch.

 

The hot surface ignitor is energized and after a 17 second warm-
up, the gas valve circuit is energized, opening the gas valve and 
igniting the burners.   After burning for about 30 seconds, the 
circulating air blower comes on, delivering warm air to the room.  
If ignition does not occur, the ignition sequence is repeated again 
up to 2 more times. (3 trials for ignition-total)

3.  After the furnace operates and satisfies the thermostat, the gas 

valve closes and the circulating air blower continues to run for 
about 2 minutes and then shuts off.  The inducer blower runs 
for 5 seconds and shuts off.

 

If  for  any  reason  ignition  and  operation  does  not  occur,  the 
control board will blink the red fault status LED, a sequence 
code, indicating what to look for as a troubleshooting guide.   
If  the  red  LED  is  ON  but  not  blinking  check  the  electronic 
temperature control to verify its operation. This can be easily done 
by disconnecting the 3 electronic temperature control leads from 
the main furnace board and using a pig tail jumper to connect 
R & W together on the board. If the furnace comes on and runs 
normally  the  temperature  control  board  is  malfunctioning.  If 
the heater still does not come on, then the main furnace board 
is malfunctioning. Look for any fault codes below and verify 
the 3 amp fuse is not blown.

OPERATION AND TROUBLESHOOTING

 ACF Greenhouses 

Summary of Contents for DV-55E

Page 1: ...his appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance Consumer Retain this...

Page 2: ...assachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 11 Lighting Instructions 12 Wiring 13 Maintenance 14 Operation and Trouble...

Page 3: ...nstallation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected beforeuseandatleastannuallybyaqualifiedserviceperson More frequent cleaning may be required due to...

Page 4: ...ights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption...

Page 5: ...naccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshall be permanently mounted to the exterior o...

Page 6: ...be performed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a th...

Page 7: ...ontrol valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the g...

Page 8: ...ning Conversion must be done by a qualified service technician Main burner orifice s and new gas conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to fur...

Page 9: ...NG The nearest point of the vent cap should be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce t...

Page 10: ...if plastic anchors are used Attach the two wall mounting brackets to the casing back by using 4 10 x 1 2 13mm hex head screws provided Figure 5 Figure 6 Figure 7 Figure 8 2 51mm TO 13 330mm 2 51mm TO...

Page 11: ...ach the right shroud and left shroud to the casing back the 3 4 wide flange on the shroud must be positioned toward the casing side When positioned correctly the 6 louvers on the shroud will be facing...

Page 12: ...lified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the therm...

Page 13: ...VAC circuit If current is below 1 micro amp remove sensor clean with light sandpaper and retest Note This heater is equipped with a remote bulb electronic thermistor control located down low at the ba...

Page 14: ...lve 4 Remove gas valve from gas valve bracket Removing Main Burner Orifice s 1 Remove front grill assembly 2 Remove burner compartment access panel 2 screws 3 Disconnect manifold union assembly 4 Disc...

Page 15: ...terminal on the board The inducer blower circuit is energized and the inducer blower comes on for 15 seconds pre purging out any gas and closing the pressure switch The hot surface ignitor is energize...

Page 16: ...essure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far from Burner...

Page 17: ...e Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of Gas...

Page 18: ...19563 3 0907 Page 18 PARTS VIEW ACF Greenhouses...

Page 19: ...19563 3 0907 Page 19 SERVICE NOTES ACF Greenhouses...

Page 20: ...3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com ACF Greenh...

Reviews: