GAS SUPPLY
The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10ft
0-3m
1/2"
12.7 mm
3/8"
9.5 mm
1/2"
12.7 mm
3/8"
9.5 mm
11-40ft
4-12m
1/2"
12.7 mm
1/2"
12.7 mm
5/8"
15.9 mm
1/2"
12.7 mm
41-100ft
13-30m
1/2"
12.7 mm
1/2"
12.7 mm
3/4"
19 mm
1/2"
12.7 mm
101-150ft
31-46m
3/4"
19 mm
1/2"
12.7 mm
7/8"
22.2 mm
3/4"
1.9 mm
Note:
Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note:
Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a
flexible appliance connector cannot exceed three feet in length.
Figure 8
Gas Supply Pressure (inches w.c.)
Minimum
Normal
Maximum
Natural Gas
4.5"
7.0"
*14.0"
LP (Propane)
10.8"
11.0"
14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas
3.5"
LP (Propane)
10.0"
*NOTE: Remote “RF” Models - 10.5” w.c. maximum
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE:
The millivolt gas controls are equipped with a captured screw
type pressure test point, therefore it is not necessary to provide a
1/8” test point up stream of the control.
When using copper or flex connector use only approved fittings.
The appliance and it’s individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
CAUTION!
If one of the procedures results in pressures in
excess of 1/2 psig (14” w.c.) (3.5 kPa) on the fireplace gas valve,
it will result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5” w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5” w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa). Propane gas models will have a manifold
pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8” w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa).
Figure 9
Summary of Contents for DVX36DP31N-3
Page 21: ...31453 6 0914 Page 21 Figure 31 Figure 29 Figure 30 EXAMPLES TOP VENT RUN ...
Page 35: ...31453 6 0914 Page 35 DVVK 4FV DIRECT VENT TERMINATION KIT cont Figure 54 ...
Page 49: ...31453 6 0914 Page 49 Figure 71 MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM ...
Page 72: ...31453 6 0914 Page 72 PARTS VIEW Note Refer to page 46 when ordering logs ...