34829-1-0115
Page 18
EXAMPLES - VENT RUN
24” MINIMUM
CLEARANCE TO
COMBUSTIBLES
24”
►
▲
◄
►
◄
►
▼
◄
EXAMPLE
If total horizontal needs to be 8', then the minimum required
vertical is 6'.
H=8' (45° + 90° + 90°) = 14' (equivalent horizontal)
From the graph the required vertical is 6'.
Figure 30 - (DV(LT,TT)42)
►
▼
◄
▲
◄
►
EXAMPLE
If total horizontal needs to be 10', then the minimum required
vertical is 6'.
H=10' (90° + 90°) = 16' (equivalent horizontal)
From the graph the required vertical is 7'.
Figure 31- (DV(LT,TT)42)