VENTING FIREPLACE
Maximum horizontal run for a minimum vertical rise
▼
20”
(508mm)
MAXIMUM HORIZONTAL RUN
WITH MINIMUM VERTICAL
RISE AND 90 ELBOW
o
12” SECTION
(DV(LT,TT)36)
24” SECTION
(DV(LT,TT)42)
Figure 24
Minimum vertical rise for maximum horizontal run
19’- 5”
(5.9M)
▲
►
▼
◄
Figure 25
Below Grade Installation
When it is not possible to meet the required vent terminal clearances
of 12" (305mm) above grade level, a snorkel kit is recommended.
It allows installation depth down to 7" (178mm) below grade level.
The 7" (178mm) is measured from the center of the horizontal vent
pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window
well with adequate and proper drainage to be installed around
the termination area.
Typical Basement Installation
►
▼
▼
▲
▲
3” (76 mm) MINIMUM
▲
▼
18”
(457 mm)
MINIMUM
▲
▼
12”
(305 mm)
ABOVE
GRADE
48”
(1219 mm)
Figure 26