31629-20-0320
Page 12
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe
Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Natural
Propane
Natural
Propane
0-10 feet
0-3 meters
1/2”
12.7 mm
3/8”
9.5 mm
1/2”
12.7 mm
3/8”
9.5 mm
10-40 feet
4-12 meters
1/2”
12.7 mm
1/2”
12.7 mm
5/8”
15.9 mm
1/2”
12.7 mm
40-100 feet
13-30 meters
1/2”
12.7 mm
1/2”
12.7 mm
3/4”
19 mm
1/2”
12.7 mm
100-150 feet
31-46 meters
3/4”
19 mm
1/2”
12.7 mm
7/8”
22.2 mm
3/4”
19 mm
NOTICE:
Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
NOTICE:
Since some municipalities have additional local codes, it
is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The Commonwealth of Massachusetts requires
that a flexible appliance connector cannot exceed three feet in length.
FLEXIBLE GAS LINE CONNECTION
GAS SUPPLY
TEE HANDLE
FLEX TUBING
FLARE FITTING
FLARE SHUT
OFF VALVE
Figure 8
Gas Supply Pressure (inches w.c.)
Minimum
Normal
Maximum
Natural Gas
4.5"
7.0"
14.0"
Propane Gas
10.8"
11.0"
14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas
3.5"
Propane Gas
10.0"
Installing a New Main Gas Shut-Off
Each appliance should have its own manual gas shut-off. A manual
main gas shut-off should be located in the vicinity of the unit. Where
none exists, or where its size or location is not adequate, contact
your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTICE:
The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary to
provide a 1/8” test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with hose fittings
for pressure checks, then reinstalled before operating fireplace.
When using copper or flex connector use only approved fittings.
The appliance and it’s individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5 kPa).
Attention!
If one of the procedures results in pressures in excess
of 1/2 psig (14” w.c.) (3.5 kPa) on the fireplace gas valve, it will
result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural Gas valves have a built-in pressure
regulator in the gas valve. Natural Gas models will have a manifold
pressure of approximately 3.5” w.c. (.871 kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5” w.c.
(1.120 kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484 kPa). Propane Gas models will have a manifold
pressure approximately 10.0” w.c. (2.49 kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8” w.c.
(2.68 kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484 kPa).
GAS LINE HOLE
(BOTH SIDES)
2”
10”
FROM FRONT OF
APPLIANCE TO
GAS LINE HOLE
Figure 9
Summary of Contents for DVD32
Page 21: ...31629 20 0320 Page 21 Figure 29 Figure 30 Figure 31 EXAMPLES TOP VENT RUN ...
Page 41: ...31629 20 0320 Page 41 Figure 61 MILLIVOLT STANDING PILOT WIRING DIAGRAM FP3 SERIES ...
Page 52: ...31629 20 0320 Page 52 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING FP7 SERIES ...
Page 53: ...31629 20 0320 Page 53 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING FP7 SERIES ...
Page 59: ...31629 20 0320 Page 59 DVD36FP 3 5 7 PARTS VIEW ...
Page 61: ...31629 20 0320 Page 61 DVD42FP 3 5 7 PARTS VIEW ...
Page 63: ...31629 20 0320 Page 63 DVD48FP 3 5 7 PARTS VIEW ...