INSTALLATION
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This
hole must be 12-5/8in high x 10-5/8in wide with its center line
determined by the amount of vertical rise and horizontal run of
the termination.
See Figure 30.
When locating the hole it must be
noted that the bottom of the cap must be 12in above the ground
level, and top of the cap must be no less than 18in below a
combustible projection, and no closer than 9in to any wall running
parallel to vent termination. Refer to “Below Grade Instatallation”
on page 25.
A1
CENTER OF ELBOW
STRAIGHT
OUT
(MINIMUM)
A2
B
C
C
B
E
D
DIMENSIONS (in inches)
A1
49-5/8
B
5-5/16
C
7-5/16
D
10-5/8
E
See top vent configuration charts for allowable A2 and E
dimensions, pages 28 and 29.
A2
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL INSTALLATIONS WITH 90 DEGREE ELBOW.
SEE FIGURE 41 ON PAGE 27 FOR PERMISSIBLE TOP VENT
HORIZONTAL AND VERTICAL DIMENSIONS.
Figure 30
Installing Support Brackets
Install a horizontal pipe support used for each 3 feet of
horizontal run to framing members. Allow 3 inches of clearance
to combustibles above 8 inch diameter pipe and elbows and 1
inches of clearance on both sides and bottom.
Support vertical runs of this vent systems every 4 feet using
wall brackets attached to the vent pipe and secured with nails or
screws to structural framing.
NOTICE:
Maintain all clearances to combustibles as shown in
Figures 6 to 8
on page 12.