Gas input for direct vent fireplace insert converted to Propane gas:

DV(D,CD)32FP7 - 18,000 BTU per hour

DV(D,CD)36FP7 - 20,000 BTU per hour

DV(D,CD)42FP7 - 25,000 BTU per hour

DVD48FP7 - 28,000 BTU per hour

The direct vent gas fireplace insert when converted to Propane 

gas will have a manifold pressure approximately 10.0" w.c. 

(2.49 kPa) at the valve outlet with the inlet pressure to the valve 

from a minimum of 10.8" w.c. (2.68 kPa) for the purpose of input 

adjustment to a maximum of 14.0" w.c. (3.48 kPa). 

INSTRUCTIONS FOR CONVERSION

1.  If the fireplace is installed, turn OFF gas and electric supply 

to fireplace before making gas conversion.

2.  Remove bottom panel, grasp panel, lift and pull forward.

3.  Release two glass frame spring clamps at bottom of firebox.

4.  Remove glass frame assembly.

5.  Remove logs from burner assembly.

6.  Remove (2) 10 x 1/2" screws from rear log support. Remove 

log support.

7.  If applicable, remove liners and burner cover.

8.  Remove four (4) 10 x 1/2" screws from burne. Grasp 

burner assembly, lift and pull to the right to remove burner 

assembly. 

9.  Use a 3/8" and 1/2" wrench to remove burner orifice.

10.  Remove Natural gas main burner orifice from orifice fitting.

11.  Install Propane gas main burner orifice into orifice fitting: 

 

for DV(D,CD)32FP7 USE ORIFICE 

MARKED #56

 

for DV(D,CD)36FP7 USE ORIFICE 

MARKED #55

 

for DV(D,CD)42FP7 USE ORIFICE 

MARKED 1.45 mm

 

 

for DVD48FP7 USE ORIFICE 

MARKED 1.55 mm

12.  Pull upward on pilot hood to remove and gain access to pilot 

injector orifice.

13.  Remove Natural gas pilot injector orifice from pilot burner 

with 5/32" hex (Allen) wrench. 

14.  Insert 

Appropriate Propane gas pilot injector orifice

 into 

pilot burner using the 5/32" hex wrench. 

15.  Re-install pilot hood to pilot assembly. Push downward to 

snap in place.

16.  Convert the gas valve as instructed in 

S.I.T. Propane Gas 

Valve Conversion Kit.

17.  Align burner assembly with the air shutter as you place 

burner assembly into the original position in firebox.

18.  Adjust air shutter setting to 

FULL Open 

on all models.

19.  Attach burner assembly with four (4) 10 x 1/2" screws from 

Step 8.

20.  Attach rear log support with (2) 10 x 1/2" screws from Step 7.

21.  The converted fireplace must be connected to a supply of 

the conversion gas and checked for leaks at all connections.

22.  Refer to Log and Ember Placement in your Installation 

Intructions and Owner's Manual to place logs onto burner 

assembly.

23.  The fireplace must be checked to ensure it is operating at 

the correct pressure of 10.0" w.c.

24.  Replace glass frame onto firebox.

25.  Secure the two glass frame spring clamps at bottom of 

firebox to secure glass door assembly.

26.  Replace bottom panel.

27.  Gas conversion is completed.

The main burner flame and pilot burner flame must be checked 

for proper flame characteristics, as outlined in the Installation 

Instructions and Owner’s Manual.

Verifying Input Rate of Converted Fireplace

The input of the fireplace must be checked as follows:

1.  Turn off all other gas appliances. Clock the gas meter and 

determine the number of seconds required to consume one 

cubic foot of gas.

2.  3600 ÷ time (in seconds) = cu. Ft. per hour.

3.  Then cu. Ft. per hour x heating value of gas = input rate 

(Btuh). On installation without gas meters, check manifold 

for proper pressure.

If fireplace is not installed or warranty card has not been returned 

to Empire Comfort System’s, Inc., check off type of gas converted 

to on card. Also, indicate conversion by adding “Conv.” behind 

type of gas.

www.empirecomfort.com

Empire Comfort Systems Inc.

Belleville, IL

If you have a general question 

about our products, please e-mail 

us at [email protected]
If you have a service or repair 

question, please contact your dealer.

Summary of Contents for DVCD32FP7

Page 1: ...ith all the requirements of the authority having jurisdiction CHECK THE SAFETY SHUTDOWN PERFORMANCE WARNING Perform the safety shutdown test any time work is done on a gas system to avoid the possibility of fire or explosion with property damage personal injury or loss of life CHECK SAFETY SHUTDOWN SYSTEM Intermittent Pilot System 1 Switch main switch to OFF position Main burner and pilot should g...

Page 2: ...y Push downward to snap in place 16 Convert the gas valve as instructed in S I T Propane Gas Valve Conversion Kit 17 Align burner assembly with the air shutter as you place burner assembly into the original position in firebox 18 Adjust air shutter setting to FULL Open on all models 19 Attach burner assembly with four 4 10 x 1 2 screws from Step 8 20 Attach rear log support with 2 10 x 1 2 screws ...

Page 3: ...URITÉ AVERTISSEMENT Exécuter un essai d arrêt de sécurité après chaque intervention sur le système de gaz afin d éviter les risques d incendie ou d explosion causant des dégâts matériels des blessures corporelles voir la perte de vie VÉRIFIER LE SYSTÈME D ARRÊT DE SÉCURITÉ Système de veilleuse intermittente 1 Placer l interrupteur principal en position OFF Arrêt Le brûleur principal et la veilleus...

Page 4: ...leuse Pousser vers l avant pour l enclencher 16 Convertir la soupape de gaz tel que mentionné dans le Nécessaire de conversion de soupape au gaz propane S I T 17 Aligner l ensemble de brûleur avec l obturateur d air lors de la mise en place du brûleur dans sa position d origine dans la chambre de combustion 18 Ajuster le réglage de l obturateur d air COMPLÈTEMENT Ouvert sur tous les modèles 19 Fix...

Reviews: