6. EXTERNAL UNIT INSTALLATION

6.1   External unit installation

- Install the anti –vibration rubber pads under the external unit (acces-

sory provided separately) and place the unit on a raised part of at 

least 10 cm as shown in Fig. A.

- Make sure about the stability and the levelling of the surface where 

unit is placed.

- When several external units have to be installed, it is essential to 

assure distances between the units which do not restrict air circu-

lation to the single units and to make maintenance operations easier 

(Fig. B) 

- In case of under roof installation or similar, please follow the indica-

tions shown in fig. C.

A

A

Fig. B

A = min 60 cm

Fig. C

min  400 mm

min  400 mm

A

A = 10 cm

Fig. A

A = 10 cm

Nota:

Fixing brackets are accessories supplied separately

6.2   Outdoor unit condensation drain pipe

The outdoor unit is provided with a hole in the lower part of the frame, 

which through a conical connection (supplied), drains the condensation 

water.

-  The rubber union attachment is a push-fit (Fig. A).

-  The condensation drain-pipeline should be slightly tilted so as to 

favour the natural outflow.

-  It is advisable to use a plastic pipe sufficiently rigid to avoid its being 

flattened.

Fig. A

Attention!

Place the condensation water outlet so that no damage may be caused 

to people or things.

It is advisable to be able to visually check the outlet drain at the end of 

the piping, or alternatively insert a transparent section in the  tubing 

itself when it flows into an outlet which cannot be inspected.

Installation and maintenance activities on the air conditioners can 

be done by personnel and companies holding appropriate certifi-

cate according to the Regulation (EC) Nr. 303/2008 which provides 

the minimum  requirements of the companies and of the personnel 

about fixed units of refrigeration, air condition and heating pumps 

which contain some fluorinated greenhouse gases, according to 

the Regulation (EC)  nr. 842/2006 of the European Parliament and 

of the Council.

- Installation must be performed by qualified and authorized personnel.

- Do not attempt to install the unit by yourself.

- For any repairs, contact the service centre.

- Repairs of an electrical nature must be performed by qualified 

  electricians.

- Improper operations may cause serious harm to the user. 

- You can find a list of service centres at the website

 

www.emmeti.com

The right installation of the air conditioner assure its efficiency

Therefore we invite you to follow the instructions carefully about positio-

ning, installation, connexions and test listed in these manuals.

CAUTION

Danger cut: use of gloves.

If the conditions are met Arrange for work at height.

Summary of Contents for XECO Series

Page 1: ...INSTALLATION MANUAL FOR EXTERNAL UNIT INSTALLATION MANUAL FOR EXTERNAL UNIT GB GB Air Conditioners Line Residential Serie XECO...

Page 2: ...the specifications and all the information useful for the correct functioning The information contained in this publication may be subject to changes at any time and without any notice whatsoever for...

Page 3: ...utdoor unit 5 3 Minimum operational distances of indoor unit 5 4 Minimum operational distances of outdoor unit 5 5 Distance between the units 5 6 Dimensions of the indoor unit 5 7 Dimensions of the ou...

Page 4: ...it is pressed the air conditioner runs in automatic mode 1 1 Composition of the air conditioner The air conditioners are of the Split System type with air air heat exchange They consist of two separat...

Page 5: ...oduct identification table The following table is for identifying the make up of the air conditioner Type Potentiality in kBtu h Model Set UI UE Outdoor Unit Indoor Unit Single HI Wall 9 XECO 0913 XEC...

Page 6: ...stall the air conditioner in rooms where gas leakages or other flammable substances could occur near the units Maintenance operations must be carried out exclusively by quali fied technicians Do not u...

Page 7: ...r condi tioner Avoid the use of heating equipments near the air conditioner Select the most suitable room temperature Be careful in rooms where there are children sick and or elderly people Do not pou...

Page 8: ...with permanent ink the factory charge of refrigerant of the product the amount of additional refrigerant for the pipes the total charge of refrigerant The completed label must be placed in a visible...

Page 9: ...ble materials Organic peroxide Exposure controls personal protection Control parameters AEL 8 h TWA 1000 ml m for each of the two components Respiratory protection For gas recovery and maintenance wor...

Page 10: ...operations have to be done carefully because the external part of the units has not to be damaged when knifes or cutters are used to open the carton package After unpacking make sure of the unit inte...

Page 11: ...bserve the minimum operational distances 5 2 Positioning the outdoor unit If possible avoid exposing the unit to direct sunlight particularly in early afternoon On the contrary provide for a suitable...

Page 12: ...e positioned with a maximum gradient of 5 metres In cases where the indoor unit is installed higher than the outdoor unit with Between 3 and 5 meters must be provided an intermediate siphon to lock oi...

Page 13: ...of the indoor unit 70 90 45 45 40 55 40 41 3 41 3 71 161 54 54 5 120 5 548 5 W D H 103 149 542 176 130 685 193 XECO 0913 W XECO 1213 W XECO 0713 XW XECO 0913 XW XECO 1813 W XECO 2413 W 55 55 55 70 70...

Page 14: ...G Model A mm B mm C mm D mm E mm F mm G mm XECO 0913E 776 540 320 712 257 510 286 XECO 1213E 848 540 320 756 257 540 286 XECO 1813E 965 700 396 890 340 560 364 XECO 2413E 1000 790 427 920 370 610 395...

Page 15: ...n Place the condensation water outlet so that no damage may be caused to people or things It is advisable to be able to visually check the outlet drain at the end of the piping or alternatively insert...

Page 16: ...n near the outdoor unit in order to enable the flare to be remade if necessary Remove any burrs from the end of the pipe using a countersink This ope ration is very important in order to obtain good q...

Page 17: ...d connection cables must be approved in conformance with IEC standards and for lengths up to 15m must have a section not less than Model Cable of alimentation Cable connection Single Hi Wall 3x2 5 mm2...

Page 18: ...with the piping make a suitable wall ancho rage by means of a cable fastener or hose clips 6 4 4 Connection to the outdoor unit terminal board Remove the two fixing screws and take off the terminal b...

Page 19: ...Dual Hi Wall L A B Alimentation Cable Connection cable Connection cable Connection with indoor unit L Terminal block external unit Trial Hi Wall L A B Connections with the internal unit Indoor Unit In...

Page 20: ...nd turn the pump off If the pressure gauge set is fitted with a vacuum gauge wait at least 5 minutes then check that the vacuum in the system has been maintained If not look for the cause of the leak...

Page 21: ...effects on the environment and health and encou rages the recycling of product materials For further detailed information regarding available collection systems please contact your local waste disposa...

Page 22: ...and indoor unit E6 OFF 3s and blink 6 times Cooling and dehumidification compressor and outdoor fan stops while the indoor fan continues to run Heating the entire unit stops Communication cable is no...

Page 23: ...w supply voltage 2 Overabundance of refrigerant 3 Ambient temperature is too high 4 Poor heat exchange exchanger dirty or poor air circulation 18 Reduced frequency due to overcurrent F8 OFF 3s and bli...

Page 24: ...igh temperature protection IPM module P8 OFF 3s and blink 19 times Cooling and dehumidification compressor and outdoor fan stops while the indoor fan continues to run Heating the entire unit stops 1 C...

Page 25: ...d 39 Abnormal outdoor fan motor L3 OFF 3s and blink 23 times The compressor stops 1 Motor wiring loose or sliced 2 Motor blocked 3 Motor damaged 4 Electronic board damaged 40 High power protection L9...

Page 26: ...stops 1 Supply voltage less than 175 V AC 2 Four way valve wiring loose or sliced 3 Four way valve damaged 4 Electronic board damaged 47 Anomaly from zero crossing of outdoor unit U9 OFF 3s and blink...

Page 27: ...erminals or con nectors FU Fuse BN Brow BK Black BU Blue YV Ivory GY Gray GN Green VT Violet OG Orange RD Red YE Yellow Swing Motor M Defective motor 4YV 4 way valve EKV Electronic expan sion valve C...

Page 28: ...28 GB GB 10 XECO 1213 XECO 1813 and XECO 2413 10 WIRING DIAGRAMS...

Page 29: ...29 10 WIRING DIAGRAMS XECO 1813D XECO 2413T GB GB...

Page 30: ...fler 4 Way valve Strainer Electronic Expansion Valve Strainer OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT Model XECO 0913 and XECO 1213 Refrigerant pipe diameter Liquid 1 4 6 mm Gas 3 8 9 52 mm INDOOR UNIT...

Page 31: ...31 kWh y kWh y kW kW kWh y kWh y kW kW kW kW kW kW 55 GB GB 12 REFRIGERATION CIRCUIT kWh y kWh y kW kW kWh y kWh y kW kW kW kW kW kW 55...

Page 32: ...32 GB GB 12 kWh y kWh y kWh y kW kW kW kWh y kWh y kWh y kW kW kW kW kW kW kW kW kW 12 REFRIGERATION CIRCUIT...

Page 33: ...33 12 REFRIGERATION CIRCUIT GB GB kWh y kWh y kWh y kW kW kW kWh y kWh y kWh y kW kW kW kW kW kW kW kW kW...

Page 34: ......

Page 35: ...reet Zip Town Country Slip A for user To be kept Please print in block letters GUARANTEE CERTIFICATE Slip A GUARANTEE CERTIFICATE Slip B GUARANTEE CERTIFICATE Slip C Model Serial Number Date installat...

Page 36: ...send part C in a closed envelope to Emmeti Spa post box nr 74 Fontanafredda PN within ten days from the date of installation first startup Should the certificate not be sent within 10 days of the ins...

Page 37: ...37 Note...

Page 38: ...Note...

Page 39: ...Note...

Page 40: ...a correct disposal the different materials must be divided and collected according to the regulations in force EMMETI Spa Via B Osoppo 166 33074 Fontanafredda frazione Vigonovo PN Italy Tel 0434 56791...

Reviews: