Radar Level Meter EMKOTDR-60| Emkometer,
s.r.o., Na Žižkově 1245, Ledeč n/S., 58401, CZ
tel/fax: 569 721 622 | tel: 569 720 539, 569 721
549
|
The maximum allowable temperature of the medium, process connection and ambient temperature depends
in
EMKOTDR-60
Xi (XiT) at the desired temperature class (see tab. Maximum temperatures for the performance
Xi (XiT) category 1/2G and tab.). The temperature value can not be exceeded, be
cause the hot surface of the
device could cause ignition of an explosive or flammable atmosphere. At the same time can not exceed the
maximum temperature for the different variants of the electrodes (Table of temperature durability).
Pressure durability (performance NT, XiT)
Variants
/ Performance
Max.
operation
pressure
for
temp.
tp
to
30°C
to
85°C
to
130°C
to
160°C
to
200°C
EMKOTDR-60
T-
10(20)
15 MPa
10 MPa
3 MPa
2 MPa
1 MPa
EMKOTDR-60
T-
11(12)
4 MPa
1,5 MPa
2 MPa
1,5 MPa
0,3 MPa
EMKOTDR-60
T-
30(33)
15 MPa
10 MPa
3 MPa
-
-
EMKOTDR-60
T-32
1 MPa
0,5 MPa
0,1 MPa
-
-
Factory default
EMKOTDR-60_-_ _
MIN
LEVEL
(Distance
to
min.
level)
according
to the length of the rod
(rope)
electrode
MAX
LEVEL
(Distance
to max.
level)
100 mm
UNITS
mm; %;
°C
DAMPING
2
SENSITIVITY
MEDIUM
MEDIUM
LIQUID
FAILURE MODE – NO
ECHO
4,00
mA
POOLING
ADDRESS
(HART
®
)
00
PASSWORD
No
password
Recommended sensitivity depending on the dielectric constant of the medium
Degrees
Sensitivity
Dielectric constant of the medium
for length of electrode to 20
for length of electrode over 20 m
8!
USER (extreme)
1,8 .. 1,9
2 .. 3
7!
USER (extreme)
1,9 .. 2
4 .. 6
6!
USER (extreme)
2 .. 3
6 .. 8
5
HIGH
3 .. 4
8 .. 10
4
USER
4 ..
6
10 .. 13
3
MEDIUM
6 .. 8
13 .. 16
2
USER
8 .. 10
16 .. 20
1
LOW
10 and more
20 and more