EMKOMETER EMKOTDR-60 Manual Download Page 25

 

 

 

Solutions for your measurements 

www.emkometer.com 

Page 

25

 of 

32

 

Radar Level Meter EMKOTDR-60| Emkometer, 

s.r.o., Na Žižkově 1245, Ledeč n/S., 58401, CZ

 

tel/fax: 569 721 622 | tel: 569 720 539, 569 721 

549 

[email protected]

 

 

i

 

a

 

Maximum  output  parameters  of  intrinsically  safe  units  must  correspond  with  limit  input  parameters  of  the 

level meter. In the evaluation of intrinsic safety of the circuit must be taken into account the parameters of the 

connected cable (especially its inductance and capacitance).

 

 

The electrode part of the 

EMKOTDR-60

Xi (XiT) can be placed in zone 0, the body with electronics can be placed 

in zone 1. In zone 20 can be placed whole level meter.

 

 

 

 

16. Use, manipulation and maintenance 

The level 

meter does not require any personnel for its operation. Follow

-

up displaying device is used to inform 

the technological entity operating personnel on the measured substance level height during the operation.

 

Maintenance of this equipment consists in verification of integrity of the level meter and of the supply cable. 

Depending on the character of the substance measured, we recommend to verify at least once per year the 

clarity of the ultrasound transducer emitting field and to clean it, respectively. In case any visible defects are 

discovered, the manufacturer or reseller of this equipment must be contacted immediately.

 

 

 

The level meter must be installed to prevent tensile overload of the rope electrode. 

 

It is forbidden to perform any modifications or interventions into the EMKOTDR-60  level meter 

without manufacturer's approval. Potential repairs must be carried out by the manufacturer or by 

a manufacturer authorized service organization only. 
Installation, commissioning, operation and maintenance of the EMKOTDR-60

 

level meter has to be 

carried out in accordance with this instruction manual; the provisions of regulations in force 

regarding the installation of electrical equipment have to be adhered to. 

 

 

 

17. Marking of labels

 

Level meters label data

 

EMKOTDR-60N(T) 

 

Symbol of producer: logo 

Emkometer  

Internet address: 

www.emkometer.cz

 

Country of origin: Made in Czech Republic

 

Level meter type: 

EMKOTDR-60N_–__–

G

–I E______ or EMKOTDR-60N _–__–

G

–M E______ 

Serial number: Ser. No.: 

____ – 

(from the left: production year, serial production number) 

 

Supply voltage: U = 18 ... 36 V=

 

Output current range: I= 4 ... 20 mA

 

Ambient temperature range: t = 

-

30 ... +70 °C

 

Protection class: IP67 

 

Compliance mark:

 

Electro-waste take-

back system mark:

 

 

 

Summary of Contents for EMKOTDR-60

Page 1: ...Doc no 207 en_man_EMKOTDR 60 7 2015 www emkometer com Radar level meters with guided wave EMKOTDR 60...

Page 2: ...tting into operation 6 6 Installation instructions 6 7 Electrical connection 12 8 Set up elements 13 9 Status signalization 13 10 SETTING 14 10 1 BASIC SETTINGS 14 10 2 Service settings 17 10 3 Additi...

Page 3: ...result in crashes in the application overfill ing of the tank or damage of system components The manufacturer is not responsible for improper use losses of work caused by either direct or indi rect da...

Page 4: ...lectrode length 2 m EMKOTDR 60 20 Uncoated stainless steel rod electrode with reference tube for accurate level measurement of liquids in cram ped spaces Maximum electrode length 3 m EMKOTDR 60 30 Unc...

Page 5: ...adar Level Meter EMKOTDR 60 Emkometer s r o Na i kov 1245 Lede n S 58401 CZ tel fax 569 721 622 tel 569 720 539 569 721 549 info emkometer cz High temperature variant EMKOTDR 60 30 T EMKOTDR 60 10 11...

Page 6: ...stallation instructions BASIC INFORMATIONS Install the level meter into the upper lid of the tank or reser voir using a welding flange or fastening nut The min distance to install the level meter into...

Page 7: ...the dead zone the level meter will not work properly The size of the dead zone is affected by the set measurement sensitivity The minimum distances to the medi um dead zones are presented in the table...

Page 8: ...he hole must be greater than the thick ness a of the concrete see Fig 8 If the thickness a of the concrete is greater than the diameter of the hole install the level meter in a recess see Fig 9 LEVEL...

Page 9: ...tank ladders vari ous partitions mixers etc does not intervene into the pro tective zone see Fig 12 If still these objects intervene into the protective zone of the level meter it is necessary to crea...

Page 10: ...he electrode must be selected so that the weight will be below the minimum measured level see Fig 16 The distance the electrode from the tank wall must be at least 300 mm Otherwise the level meter ins...

Page 11: ...ommend to preload the rope elec trode by tension force of about 100 N Rope electrode level meter must untangle and then can be inserted into the tank VARIANT WITHOUT ELECTRODE Type of level meter with...

Page 12: ...o the diagram in Fig 20 Tighten the bolten clips and the cable bushing 6 Insert display module to the level meter 7 Slip the silicone seal on thread of level me ter and tighten the nut of the upper li...

Page 13: ...ed to join the display module Once set the display module can be disconnected and the level meter can measure without him 9 Status signalization displej funkce NO ECHO Lighting intermittently the leve...

Page 14: ...lue 10 1 Basic settings After the first start of the level meter it is necessary to perform the basic configuration setting of the measuring range choice of units possibly damping sensitivity and teac...

Page 15: ...gal bbl mA 1 To enter to the menu press the same button to select BASIC SETTINGS Then using and select UNITS 2 Now the menu item UNITS is shown By pressing the and button make the settings of individ...

Page 16: ...of the medium 1 Pressing the button xxx is for enter the menu press the same button to select the item BASIC SETTINGS Then by pressing the buttons xxx and xxx is selected the item SENSITIVITY 2 Using...

Page 17: ...or HART communication Here you can set the sensor into the initial state or reset it as well The set tings are accessible in the basic menu under the item SERVICE ELECTRODE Setting of the length and t...

Page 18: ...NO ECHO Current in case of echo loss The values can be set in fi steps 3 75 mA 4 mA 20 mA 22 mA LAST last measured data HART HART mode point to point multidrop and multidrop mode address setting Up t...

Page 19: ...mations about actual value of distance to level from level meter DISTANCE TO LEVEL and about current flowing through the loop CURRENT It can be used for example to check the settings of the connected...

Page 20: ...g the password 1 Use the buttons and in the menu PASSWORD to select the mode ENTER for entering the pass word or the mode CHANGE for changing the password when activated the words are displayed in ver...

Page 21: ...date of the level meter type serial number SN and firmware version SW 11 HART communication protokol Universal communication interface for data communication of peripheral devices with the level mete...

Page 22: ...he electrode holder 4 Let the glued junction to harden as recommended by the glue manufacturer then the level meter is ready for installation 5 After an installation into an empty tank set a new level...

Page 23: ...33 1 If necessary remove the rod or rope electrode from the electrode holder see points 1 and 2 of The procedure of replacement of the measuring electrode 2 Rod electrodes are advised to be shortened...

Page 24: ...erload Protection against dangerous contact is secured by low safety voltage that complies with EN 33 2000 4 41 Electromagnetic compatibility according to EN 55022 B EN 61326 Z1 and EN 61000 4 2 to 6...

Page 25: ...once per year the clarity of the ultrasound transducer emitting field and to clean it respectively In case any visible defects are discovered the manufacturer or reseller of this equipment must be con...

Page 26: ...ally safety FTZ 13 ATEX 0212X Protection class IP67 Compliance mark No of authorized person examining control of system quality 1026 Electro waste take back system mark Level meters label data EMKOTDR...

Page 27: ...r your measurements www emkometer com Page 27 of 32 Radar Level Meter EMKOTDR 60 Emkometer s r o Na i kov 1245 Lede n S 58401 CZ tel fax 569 721 622 tel 569 720 539 569 721 549 info emkometer cz 18 Me...

Page 28: ...2 for measur sensitivity low medium user 1 4 high user 5 user 6 7 user 8 100 0 mm 3 150 50 mm 3 200 50 mm 3 250 50 mm 3 ElectricalparametersforvariantsXi XiT max internalvalues Ui 30V DC Ii 132mA Pi 0...

Page 29: ...The length of dead zone is 110 mm at the end of rope electrode 4 Level meter displays last measured value 5 Including 250R resistor in case of HART connection 6 hatched space applies for set measurem...

Page 30: ...r 1 4571 AISI 316 Ti St Steel W Nr 1 4301 AISI 304 St Steel W Nr 1 4404 AISI 316 L Electrode coating EMKOTDR 60 11 EMKOTDR 60 12 EMKOTDR 60 32 EMKOTDR 60 34 35 PFA FEP FEP PA Reference tube EMKOTDR 60...

Page 31: ...70 C EMKOTDR 60T 11 12 40 C 200 C 40 C 200 C 30 C 70 C EMKOTDR 60T 30 33 40 C 200 C 40 C 130 C 30 C 70 C EMKOTDR 60T 32 40 C 130 C 40 C 130 C 30 C 70 C EMKOTDR 60T 34 35 40 C 95 C 40 C 130 C 30 C 70 C...

Page 32: ...ance NT XiT Variants Performance Max operation pressure for temp tp to 30 C to 85 C to 130 C to 160 C to 200 C EMKOTDR 60T 10 20 15 MPa 10 MPa 3 MPa 2 MPa 1 MPa EMKOTDR 60T 11 12 4 MPa 1 5 MPa 2 MPa 1...

Reviews: