Generator Start Delay

Remote Start Delay

Warmup Time

Horn Duration

Generator Fail Delay

The unit instructs the generator to start and waits for the period of this timer for the generator to
become available. If it isn't available when the timer expires, the generator start failure alarm is
occurred.

This timer dictates how long the unit will wait after it has received a mains failure signal before it will
attempt to start. This prevent un-necessary starting on a fluctuating mains supply etc.

unit

This timer is initiated once the engine is up and running. It delays loading the generator until it has
stabilised. Once this timer is expired the 'Close generator' signal will be given and the generator is
available to be loaded.

the external horn and the internal sounder

unit

This timer dictates how long the

will wait after it has received a remote start signal before it will

attempt to start. This prevent un-necessary starting on a fluctuating mains supply etc.

This timer dictates how long

will work after the last error

detected. Once after this timer ended

will do the external horn and the internal sounder reset.

48

4.2.9 Timers

Note:

dis = disable

Min

Default

START TIMERS (

)

Timers->Start timers

Max

Remote Start Delay
Generator fail delay

4

0

3600

45

0

250

Horn Duration

60

0 (dis)

999

Remote start delay
Generator fail delay

Horn duration

Generator Start Delay

0

0

9999

Generator start dely

Unit

Sec
Sec

Sec

Sec

Warmup Time

5

0

250

Warming up time

Sec

Min

Default

STOPPING TIMERS (

)

Timers->Stopping timers

Max

Remote Stop Delay
Cooling Time

4

0

250

60

0 (dis) 3600

Fail To Stop Time

30

15 999

Remote stop delay
Cooling time
Fail to stop delay

Unit

Sec
Sec
Sec

Remote Stop Delay

Cooling Timer

Fail To Stop Time

This timer dictates how long the unit will wait after it has received a remote stop signal before it will
attempt to stop. This prevent un-necessary stopping on a fluctuating mains supply etc.

unit

a 'Fail To Stop' alarm signal and it

the

engine to come to rest

This is the time the generator is to run off-load once the load transfer signal has ceased. This gives the
engine time to cool down before shutdown.

Once the

has given a shutdown signal to the engine it expects the engine to come to rest. It

monitors the Generator voltage and frequency sources and if they still indicate engine movement when
this timer expires a 'Fail To Stop' alarm signal is generated.

if this parameter was selected as

maximum value (999), the unit doesn’t monitor

accepts that

.

Note:

Summary of Contents for TRANS-ATS.D

Page 1: ...Introduction Manual ENG TRANS ATS_D 02 V04 12 21 TRANS ATS D AUTOMATIC TRANSFER SWITCH User Manual...

Page 2: ...4 2 6 Engine 4 2 7 Inputs 4 2 8 Outputs 4 2 9 Timers 4 2 10 Expansion Modules 4 2 11 User Adjustment 2 1 Unit Configuration 2 2 Panel Mounting Figure 2 1 Front View 2 3 Electrical Connection 3 Definit...

Page 3: ...nt to Annex II of Directive 2011 65 EU This declaration is based on the full compliance of the products with the following European standards EN 61010 1 2010 Safety Requirements for Electrical Equipme...

Page 4: ...es the voltage monitoring for both sources and automatic transfer switching In the event of any Source voltage failure the remote start relay output is energized and the unit automatically transfers t...

Page 5: ...ing installation of this product please read the instruction manual and warnings below carefully 2 Installation indekiler 2 1 Unit Configuration indekiler 2 2 Panel Mounting The unit is designed for p...

Page 6: ...e Output 6 5A USB FUSE 7 FUSE 8 Configurable Output 3 39 38 37 36 Configurable Output 4 TRANSISTOR OUTPUTS MAX 1 A BATTERY Emergency Stop or Configurable Input 1 6 2 7 3 8 8A 8A 1 4 9 10 5 L1 S2 GENER...

Page 7: ...ge and frequency is within limits and is ready to take over the load Th LED shows that the load is the Source 1 is supplied from Th LED shows that the load is supplied from the Source 2 is 8 This LED...

Page 8: ...MING Mode This button will silence the alarm horn after a failure has been detected This button opens or closes the S1 contactor only operative when manual mode is selected This button opens or closes...

Page 9: ...cy Source 2 phase sequence Dual working time left for source 2 9 Data display pages on the LCD display S1 MAINS V12 380V V1 220V V23 380V V2 220V V31 380V V3 220V S2 on load S1 MAINS Phase seq L1 L2 L...

Page 10: ...ER SUPPLY Battery volt 12 0Vdc S2 on load INPUT OUTPUT 1 4 5 8 Inputs 0000 0000 Outputs 0000 0110 S2 on load Input Output Status Page Inputs 1 2 3 4 5 6 7 8 Outputs 1 2 3 4 5 6 7 8 Input status inform...

Page 11: ...1 Warning Alarm Page 1 3 Emergency stop The first message of current alarms This message indicates that an emergency stop alarm has occurred Event Log Page1 1 1 Emergency stop V1 I1 V2 I2 The first pa...

Page 12: ...me 0 00 Fq 50 0Hz S2 on load S2 GENERATOR S2 on load V12 380V V1 220V V23 380V V2 220V V31 380V V3 220V LOAD P1 170kW P2 170kW P3 170kW S2 on load LOAD Q1 40kVAr Q2 40kVAr Q3 40kVAr S2 on load S2 GENE...

Page 13: ...ish to change Press the Enter button LCD DISPLAY Language ENGLISH LCD DISPLAY Language ENGLISH Press the Enter button to confirm the changed value Press the Escape button to exit language selection sc...

Page 14: ...Enter button to confirm the changed value PROGRAM Operator setting Technician setting Factory adjustment PROGRAM Operator setting Technician setting Factory adjustment TECHNICIAN SETTING Password 016...

Page 15: ...quency Source 1 Reset Over Frequency Under freq trip Under freq reset Over freq trip Over freq reset Unit 4 1 1 Source 1 Mains 4 1 2 Source 2 Generator 600 60 60 60 600 600 600 VV VV VV VV 60 Min Defa...

Page 16: ...io is for additional voltage transformers mounted the unit Type of AC System Phase Sequence This parameter is used to detail the type of AC system to which the unit is connected 1 phase 2 wire 3 phase...

Page 17: ...urce supplies the load during Source dual timer If the source that supplies the load fails then the other source supplies the load When the dual time expired if the other source is failed then source...

Page 18: ...LOSE TIMER if S1 closed input selected S1 OPEN BREAKER RELAY TYPE S1 OPEN TIMER if S1 closed input selected BREAKER CLOSE PULSE TIME if S2 Close Breaker Relay Type or S1 Close Breaker Relay Type param...

Page 19: ...the S2 close timer is cancelled If the timer expires and the Source 2 Closed Auxiliary has not become active the module will issue a Source 2 failed to close alarm Source 1 Source 1 Source 1 This is...

Page 20: ...r MCB breaker and after that the unit want to give close command the same breaker this time for between open and close commands because if there is no delay between open and close commands can be prob...

Page 21: ...If this parameter is selected as Yes the unit s parameters back to factory sets After this parameter is reset automatically to No Day of week 1 Monday 2 3 4 5 6 7 Tuesday Wednesday Thursday Friday Sa...

Page 22: ...Source 1 Volt level Max Source 1 Under Voltage Source 1 Under Voltage Reset Source 1 Over Voltage Source 1 Reset Over Voltage 320 340 440 420 S1 Under volt trip S1 Under volt reset S1 Over volt trip...

Page 23: ...elay S2 fail delay ENABL DISBL ENABL DISBL ENABL DISBL sec sec 0 0 99 99 2 2 Look Source Failure at Stop Mode En Dis This parameter is only used if Source is selected as Mains supply Always Look Sourc...

Page 24: ...wn Alarm And Shutdown Load 0 1 2 3 Over Current Actions Disable Warning Alarm Only No Shutdown Electrical Trip Alarm Off Load Generator Followed By Shutdown After Cooling Shutdown Alarm And Shutdown 9...

Page 25: ...xercise function is started at 12 20 o clock 1 Monday 2 3 4 5 6 7 Period Day of week Start time Min Default EXERCISE Engine Exercise Max 0 dis 99 dis 1 7 0 0 23 59 0 00 1 Time of Period Week Start tim...

Page 26: ...59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00...

Page 27: ...ist 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset Button 6 Simulate Auto Button 7 Simulate Test Button 8 Si...

Page 28: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 29: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 30: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 31: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 32: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 33: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 34: ...ivation Select from list Active delay If Select From List 0 Remote Start On Load 1 Remote Start Off Load 2 Auxiliary S1 Fail 3 Auxiliary S2 Fail 4 Simulate Horn Reset Button 5 Simulate Alarm Reset But...

Page 35: ...fault Unit CONF EXP INPUT 2 Inputs Conf exp input 2 Max 0 2 2 0 dis 1 0 4 2 0 2 250 0 Sec 0 1 0 2 5 Dis user conf or list Polarity Indication Activation Select from list Active delay The same as Expan...

Page 36: ...sion Config Input 1 options Input active delay Input active delay Input active delay Input active delay Input active delay 21 21 21 21 21 The same as Expansion Config Input 1 options The same as Expan...

Page 37: ...h button This input mimic s the operation of the Start button and is used to provide a remotely located start push button This input mimic s the operation of the Stop button and is used to provide a r...

Page 38: ...f the Auto Start Inhibit signal become active once more it will be ignored until the unit has returned the source supply on load and shutdown This input is used to provide security to the installation...

Page 39: ...58 RESERVED 59 SOURCE 2 STOPPING For generator application 60 SOURCE 2 OPEN BREAKER 61 HORN OUT LATCHED 62 HORN OUT PULSED 63 LAMP TEST 64 RESERVED 65 SOURCE 1 AVAILABLE 66 SOURCE 1 AT REST For gener...

Page 40: ...s Conf output 6 CONF EXP OUTPUT 1 Outputs Conf exp output 1 CONF EXP OUTPUT 2 Outputs Conf exp output 2 CONF EXP OUTPUT 3 Outputs Conf exp output 3 CONF EXP OUTPUT 4 Outputs Conf exp output 4 CONF EXP...

Page 41: ...warning electrical trip or shutdown alarm has been activated This output indicates that an electrical trip alarm has been activated This output can only be reset by removal of the fault and by then pr...

Page 42: ...occurred alarm has occurred This output indicates that expansion configurable input 7 alarm has occurred 24 DIGITAL INPUT2 25 DIGITAL INPUT3 26 DIGITAL INPUT4 27 DIGITAL INPUT5 28 DIGITAL INPUT6 30 E...

Page 43: ...o be used to indicate a failure of the source 2 contactor or breaker It can only be used if the unit is configured to use Source 2 closed auxiliary feedback This output indicates that the unit has sen...

Page 44: ...used if the unit is configured to use Source 1 closed auxiliary feedback This output source has intended to be used to indicate a failure of the Source 1 contactor or breaker It can only be used if th...

Page 45: ...or the Source 1 This output indicates that the over current pre alarm has been reached for the Source 2 This output indicates that the over current trip level has been reached for the Source 2 This ou...

Page 46: ...mode The output indicates that the unit is in the Test mode This output indicates that the under current pre alarm has been reached This output indicates that the under current trip level has been rea...

Page 47: ...is being controlled remotely This output indicates that the output can be energised or de energised remotely This ouput becomes active when Source 2 s active power drops below the Reverse Power Set va...

Page 48: ...rs Note dis disable Min Default START TIMERS Timers Start timers Max Remote Start Delay Generator fail delay 4 0 3600 45 0 250 Horn Duration 60 0 dis 999 Remote start delay Generator fail delay Horn d...

Page 49: ...DISBL Unit DIAL UP ETHERNET Expansion modules Dial up Ethernet Expansion Module Selection Dal up Ethernet Call Back Selection Disable enable select Call back selection Min Default Max DISBL DISBL ENAB...

Page 50: ...r adjustment Source 2 voltage offset Max 0 0 0 20 20 20 Source 2 V1 offset Source 2 2 V offset Source 2 3 V offset Source 2 V1 Offset Source 2 2 V Offset Source 2 3 V Offset 20 20 20 VV VV VV Min Defa...

Page 51: ...ource 1 S1 Under pow prealr Under power prealarm for source 1 S1 Under pow trip Under power Error for source 1 S1 break close fail Source 1 breaker not closed alarm S1 breaker open fail Source 1 break...

Page 52: ...cur prealr Under current pre alarm for source 1 S1 Under pow alarm Under power error for source 1 S1 Under pow prealarm Under power pre alarm for source 1 S1 break close fail Source 1 breaker not clo...

Page 53: ...0 VDC for max 50 ms during cranking battery voltage should be at least nominal voltage before cranking 8 to 32 V accuracy 1 FS resolution 0 1 V 3 Resolution 1 V 5 to 99 9Hz min 20 VAC Ph N Accuracy 0...

Page 54: ...Ticaret A TURKEY Emko Elektronik Sanayi ve Ticaret A Bursa Organize Sanayi B lgesi Fethiye OSB Mah Ali Osman S nmez Bulvar 2 Sokak No 3 16215 Nil fer BURSA TURKEY Phone 90 224 261 19 00 Fax 90 224 261...

Reviews: