CONF. OUTPUT-1 (
)
Outputs->Conf. output-1
Max
0
1
0
129
0
71
Polarity
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
39
4.2.8 Outputs
0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY SOURCE 1 FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-AUXILIARY SOURCE 2 FAILURE
10-RESERVED
11-RESERVED
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-RESERVED
17-RESERVED
18-RESERVED
19-SOURCE 1 CRANK RELAY ENERGISED (For generator application)
20-COOLING DOWN TIMER IN PROGRESS
21-SOURCE 2 CRANK RELAY ENERGISED (For generator application)
22-DELAYED ALARM ACTIVE
23-DIGITAL INPUT1 ACTIVE
24-DIGITAL INPUT2 ACTIVE
25-DIGITAL INPUT3 ACTIVE
26-DIGITAL INPUT4 ACTIVE
27-DIGITAL INPUT5 ACTIVE
28-DIGITAL INPUT6 ACTIVE
29-DIGITAL INPUT7 ACTIVE
30-EXPANSION INPUT1 ACTIVE
31-EXPANSION INPUT2 ACTIVE
32-EXPANSION INPUT3 ACTIVE
33-EXPANSION INPUT4 ACTIVE
34-EXPANSION INPUT5 ACTIVE
35-EXPANSION INPUT6 ACTIVE
36-EXPANSION INPUT7 ACTIVE
37-EXPANSION INPUT8 ACTIVE
38-DIGITAL INPUT8 ACTIVE
39-EMERGENCY STOP
40-FAILED TO START SOURCE 2 (For generator application)
41-FAILED TO STOP SOURCE 2(For generator application)
42-FAILED TO START SOURCE 1 (For generator application)
43-FAILED TO STOP SOURCE 1(For generator application)
44-RESERVED
45-SOURCE 2 AT REST(For generator application)
46-SOURCE 2 AVAILABLE
47-SOURCE 2 CLOSED AUXILIARY
48-SOURCE 2 FAIL TO CLOSE
49-SOURCE 2 FAIL TO OPEN
50-SOURCE 2 HIGH FREQUENCY
51-SOURCE 2 FAILURE
52-SOURCE 2 HIGH VOLTAGE
53-RESERVED
54-SOURCE 2 LOAD INHIBIT
55-SOURCE 2 LOW FREQUENCY
56-RESERVED
57-SOURCE 2 LOW VOLTAGE
58-RESERVED
59-SOURCE 2 STOPPING(For generator application)
60-SOURCE 2 OPEN BREAKER
61-HORN OUT LATCHED
62-HORN OUT PULSED
63-LAMP TEST
64-RESERVED
65-SOURCE 1 AVAILABLE
66-SOURCE 1 AT REST
(For generator application)
67-SOURCE 1 STOPPING
(For generator application)
68-SOURCE 1 CLOSED AUXILIARY
69-SOURCE 1 FAIL TO CLOSE
70-SOURCE 1 FAIL TO OPEN
71-SOURCE 1 FAILURE
72-SOURCE 1 HIGH FREQUENCY
73-SOURCE 1 HIGH VOLTAGE
74-SOURCE 1 LOAD INHIBIT
75-SOURCE 1 LOW FREQUENCY
76-SOURCE 1 LOW VOLTAGE
77-SOURCE 1 OPEN BREAKER
78-SOURCE 2 NO LOADING COMMAND
79-SOURCE 1 NO LOADING COMMAND
80-SOURCE 1 OVER CURRENT PREALARM
81-SOURCE 1 OVER CURRENT
82-SOURCE 1 OVER POWER PREALARM
83-SOURCE 2 OVER CURRENT PREALARM
84-SOURCE 2 OVER CURRENT
85-SOURCE 2 OVER POWER PREALARM
86-SOURCE 2 OVER POWER SHUTDOWN
87-SOURCE 1 OVER POWER SHUTDOWN
88-RESERVED
89-PANEL LOCK
90-RESERVED
91-RESERVED
92-RESERVED
93-REMOTE START SOURCE 1 (For generator application)
94-REMOTE START SOURCE 2 (For generator application)
95-SOURCE 1 SHORT CIRCUIT
96-SOURCE 2 SHORT CIRCUIT
97-RESERVED
98-SOURCE 1 STOP RELAY ENERGISED (For generator application)
99-STARTING ALARM ARMED
100-SOURCE 2 STOP RELAY ENERGISED (For generator application)
101-SYSTEM AUTO MODE
102-SYSTEM MANUAL MODE
103-SYSTEM STOP MODE
104-SYSTEM TEST MODE
105-SOURCE 2 UNDER CURRENT PREALARM
106-SOURCE 2 UNDER CURRENT
107-SOURCE 2 UNDER POWER PREALARM
108-SOURCE 2 UNDER POWER SHUTDOWN
109-RESERVED
110-WAITING FOR SOURCE 1 (For generator application)
111-WAITING FOR SOURCE 2 (For generator application)
112-RESERVED
113-LOAD SUPPLY SOURCE 2
114-LOAD SUPPLY SOURCE 1
115-SOURCE 1 UNDER CURRENT PREALARM
116-SOURCE 1 UNDER CURRENT
117-SOURCE 1 UNDER POWER PREALARM
118-SOURCE 1 UNDER POWER SHUTDOWN
119-RESERVED
120-RESERVED
121-RESERVED
122-REMOTE CONTROL ACTIVE
123-SOURCE 2 REVERSE POWER
124-SOURCE 1 REVERSE POWER
125-RESERVED
126-RESERVED
127-RESERVED
128-RESERVED
129-REMOTE OUTPUT