4.2.3 Source 2(Generator)
600
60
60
60
600
600
600
V
V
V
V
V
V
V
V
60
Min
Default
SOURCE 2 VOLT LEVEL (Source 2
)
->Volt level
Max
Source 2 Under Voltage
Source 2 Under Voltage Reset
Source 2 Over Voltage
Source 2
Reset
Over Voltage
320
340
440
420
S2 Under volt trip
S2 Under volt reset
S2 Over volt trip
S2 Over volt reset
Unit
Min
Default
SOURCE 2
Source 2
FREQ. LEVEL (
)
->
level
Frequency
Max
Source 2 Under Frequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
Source 2
Reset
Under Frequency
Source 2 Over Frequency
Source 2
Reset
Over Frequency
S2 Under freq trip
S2 Under freq reset
S2 Over freq trip
S2 Over freq reset
Unit
Min
Default Unit
SOURCE 2
(Source 2
)
ACTIONS
->
Actions
Max
Look
Failure at Stop Mode En/Dis
Source 2
Always Look Source 2 Return Delay
Source 2 return delay
Source 2 fail dlelay
S2 fail.stop mode
S2 always return delay
S2 return delay
S2 fail delay
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
sec
sec
0
0
99
99
2
2
Look Source
Failure at Stop Mode En/Dis
(This parameter is only used if Source
is selected as `Mains` supply)
Always Look Source
Return Delay
(This parameter is only used if Source
is selected as `Mains` supply)
2
2
2
2
ENABLE: As soon as the module detects a source 2 failure the source 2 contactor or breaker relay will
be opened to remove the supply from the load. This is to prevent damage to the load in case of single-
phase failure.
DISABLE: In the event of a source 2 failure the unit will attempt to maintain the supply to the load for
the incoming AC source 2 supply until the source 1 is available to go on load. In the event of a
source 1 failure the module will default back to the incoming AC Source 2 supply.
ENABLE: T
DISABLE: T
is
available to go on load
he module will always wait the Source 2 Return Delay parameter before transferring the
load back to source 2.
he module will wait the Source 2 Return Delay parameter while only the source 1
before transferring the load back to source 2.
23