29
Note:
dis = disable
Min
Default Unit
Max
1
2
2
0(dis)
1
0
4
2
0
0
250
0
Sec
0
0
0
26
11
1
0- Disable
1- User Configured
2- Select From List
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
If User Configured
0- Status
1- Warning Non-Latching
2- Warning Latching
3- Electrical Trip
4- Shutdown
If User Configured
0- Active From Starting
1- Active From Safety On
2- Always Active
Input active delay
CONF. INPUT-3 (
)
Inputs->Conf. Input-3
Dis,user conf.or list
Polarity
Indication
Activation
Select from list
Active delay
If Select From List
0-Remote Start On Load
1-Remote Start Off Load
2-Auxiliary S1 Fail
3-Auxiliary S2 Fail
4-Simulate Horn Reset Button
5-Simulate Alarm Reset Button
6-Simulate Auto Button
7-Simulate Test Button
8-Simulate Manual Button
9-Simulate Start Button
10-Simulate Stop Button
11-S2 Closed Auxiliary
12-S2 Load Inhibit
13-S1 Closed Auxiliary
14-S1 Load Inhibit
15-Auto Restore Inhibit
16-Auto Start Inhibit
17-Panel Lock
18-Scheduled Run Inhibit
19-Reserved
20-Transfer Source 1 To Source 2
21-Transfer Source 2 To Source 1
22-Remote Inhibit
23-Auxiliary S1 Ready
24-Auxiliary S2 Ready
25-Simulate S1 Available
26-Simulate S2 Available