19
1s
S2CB close
command
brOP
brCP
sPLD
brCP
brCP
S2bCt
S2bCt
1s
brOP
brCP
sPLD
brCP
S2bCt
1s
brOP
brCP
sPLD
brCP
S2bCt
brCP
S2bCt
brCP
S2bCt
brCP
S2bCt
rtNB
S2CB open
command
Feedback
input
S2CB fail to
close alarm
t[s]
t[s]
t[s]
t[s]
S2CB close
command
S2bOt
S2CB open
command
Feedback
input
S2CB fail to
open alarm
t[s]
t[s]
t[s]
t[s]
brOP
S2bOt
Example-2: S2CB Open Diagram
S2bOt:
brOP:
.
If Hardware Breaker Selection parameter is selected as 2 (Motorised Breakers), S2 Close Breaker
Relay Type parameter is selected as 1 (PULSE) and S2 Open Breaker Relay Type parameter is
selected as 1 (PULSE);
S2 open timer
Breaker open pulse time
S2 Close Timer
S2 Open Timer
Source 1 Close Timer
This is used to monitor the closure of the Source 2 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 2 Closed Auxiliary’ and connected to the auxiliary on the source
2 contactor or breaker. Once a source 2 closed signal is issued the ‘S2 close timer’ is initiated. Should
the ‘Source 2 Closed Auxiliary’ input become active the timer the ‘S2 close timer’ is cancelled. If the
timer expires and the ‘Source 2 Closed Auxiliary’ has not become active the module will issue a
‘Source 2 failed to close’ alarm.
Source 1
Source 1
Source 1
This is used to monitor the opening of the Source 2 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 2 Closed Auxiliary’ and connected to the auxiliary on the
Source 2 contactor or breaker. Once a Source 2 open signal is issued the ‘S2 open timer’ is initiated.
Should the ‘Source 2 Closed Auxiliary’ input become in-active the timer ‘S2 open timer’ is cancelled. If
the timer expires and the ‘Source 2 Closed Auxiliary’ has not become in-active the module will issue a
‘Source 2 failed to open’ alarm.
This is used to monitor the closure of the Source 1 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 1 Closed Auxiliary’ and connected to the auxiliary on the
Source 1 contactor or breaker. Once a Source 1 closed signal is issued the ‘Source 1 close timer’ is
initiated. Should the ‘Source 1 Closed Auxiliary’ input become active the timer the ‘
close
timer’ is cancelled. If the timer expires and the ‘
Closed Auxiliary’ has not become active the
module will issue a ‘
failed to close’ alarm.