44
58 RESERVED
59 SOURCE 2 STOPPING
SOURCE 2
61 HORN OUTPUT LATCHED
62 HORN OUTPUT PULSED
64
65 SOURCE 1 AVAILABLE
66 SOURCE 1 AT REST
67 SOURCE 1 STOPPING
68 SOURCE 1 CLOSED AUXILIARY
69 SOURCE 1 FAILED TO CLOSE
70 SOURCE 1 FAILED TO OPEN
71 SOURCE 1 FAILURE
72 SOURCE 1 HIGH FREQUENCY
73 SOURCE 1 HIGH VOLTAGE
74 SOURCE 1 LOAD INHIBIT
75 SOURCE 1 LOW FREQUENCY
76 SOURCE 1 LOW VOLTAGE
This output indicates that the engine 2 has been instructed to stop but has not come to rest.
This output used to control the load switching device. For Details see: "BREAKERS Page" section.
This output indicates that the latched horn alarm has occurred.
This output indicates that the pulsed horn alarm has occurred.
This output indicates when the generator 1 is ready to accept load, i.e. warm up timer has timed out.
The output indicates that the generator 1 is not running.
This output indicates that the engine 1 has been instructed to stop but has not come to rest.
This output indicates that a digital input that has been configured as 'Source 1 closed auxiliary' is active.
This output source has intended to be used to indicate a failure of the Source 1 contactor or breaker. It can only
be used if the unit is configured to use ‘Source 1 closed auxiliary' feedback.
This output source has intended to be used to indicate a failure of the Source 1 contactor or breaker. It can only
be used if the unit is configured to use ‘Source 1 closed auxiliary' feedback.
This output indicates that the unit has sensed that a failure of the Source 1. This output will become active
whenever the Source 1 voltage or frequency goes out of limits, or if the auxiliary Source 1 failure input active (if
used) and the Source 1 fail timer has expired.
This output indicates that the unit has sensed that the incoming Source 1 frequency has exceeded the frequency
limit setting.
This output indicates that the unit has sensed that the incoming Source 1 voltage has exceeded the voltage limit
setting.
This output indicates that a digital input has been configured as 'Soruce 1 load inhibit' is active.
This output indicates that the unit has sensed that the incoming Source 1 frequency has fallen below the
frequency setting.
This output indicates that the unit has sensed that the incoming Source 1 voltage has fallen below the voltage
limit setting.
60
OPEN BREAKER
63 LAMP TEST
This output indicates that the module is performing a lamp test. Once the lamp test completed, the output will
become inactive again. The output can be used to feed a lamp test on external modules or panel lamps.
RESERVED