12
Unidrive M300 Quick Start Guide
Issue Number: 4
Table 4-2 Braking resistor resistance and power rating (200 V)
Table 4-3 Braking resistor resistance and power rating (400 V)
* Resistor tolerance: ±10 %
4.3 Ground leakage
The ground leakage current depends upon whether the internal EMC filter is installed or not. The
drive is supplied with the filter installed. Instructions for removing the internal filter are given in
section 4.5.1
Internal EMC filter
on page 20.
With internal filter installed:
Size 1:
2.5 mA* AC at 230 V 50 Hz (line to line supply, star point ground)
9.2 mA* AC at 230 V 50 Hz (line to neutral supply, star point ground)
Size 2:
9.36 mA* AC at 110 V, 50 Hz (2 phase, line to line supply, star point ground)
16.4 mA* AC at 110 V, 50 Hz (1 phase, line to neutral supply, star point ground)
5.3 mA* AC at 230 V, 50 Hz (3 phase supply, star point ground)
Model
Minimum
resistance*
Ω
Instantaneous
power rating
kW
Continuous
power rating
kW
01200017
130
1.2
0.25
01200024
0.37
01200033
0.55
01200042
0.75
02200024
68
2.2
0.37
02200033
0.55
02200042
0.75
02200056
1.1
02200075
1.5
03200100
45
3.4
2.2
04200133
22
6.9
3.0
04200176
4.0
Model
Minimum
resistance*
Ω
Instantaneous
power rating
kW
Continuous
power rating
kW
02400013
270
2.3
0.37
02400018
0.55
02400023
0.75
02400032
1.1
02400041
1.5
03400056
100
6.1
2.2
03400073
3
03400094
4
04400135
50
12.2
5.5
04400170
7.5
Unidrive M300 Quick Start Guide English Iss4.book Page 12 Wednesday, July 16, 2014 8:38 AM