Unidrive M / Unidrive HS Modular Installation Guide
97
Issue Number: 5
Table 6-9 24 Vdc Supply connections
* Terminal 9 on Unidrive M702 and HS72
The working voltage range of the control 24 V power supply is as follows:
* Terminal 9 on Unidrive M702 and HS72
Minimum and maximum voltage values include ripple and noise. Ripple and noise values must not exceed 5 %.
The working range of the 24 V power supply is as follows:
Figure 6-16 Location of the 24 Vdc power supply connection on size 9 to 11
Function
Sizes 9-11
Supplement the drive’s internal supply
Terminal
1, 2*
Back-up supply for the control circuit
Terminal
1, 2*
51, 52
1
0V common
2
+24 Vdc *
Nominal operating voltage
24.0 Vdc
Minimum continuous operating voltage
19.2 V
Maximum continuous operating voltage
28.0 V
Minimum start up voltage
21.6 V
Maximum power supply requirement at 24 V
40 W
Recommended fuse
3 A, 50 Vdc
51
0V common
52
+24 Vdc
Size 9 to 11
Nominal operating voltage
24.0 Vdc
Minimum continuous operating voltage
19.2 Vdc
Maximum continuous operating voltage
30 Vdc (IEC),
26 Vdc (UL)
Minimum startup voltage
21.6 Vdc
Maximum power supply requirement
60 W
Recommended fuse
4 A @ 50 Vdc
51 52
51 52
Summary of Contents for unidrive m
Page 157: ......
Page 158: ...0478 0141 05 ...