Unidrive M / Unidrive HS Modular Installation Guide
Issue Number: 5
7.1.18 Overall dimensions
H
Height including surface mounting brackets
W Width
D
Projection forward of panel when surface mounted
F
Projection forward of panel when through-panel mounted
R
Projection rear of panel when through-panel mounted
Table 7-18 Overall drive dimensions
7.1.19 Weights
Table 7-19 Overall drive weights
7.1.20 Safe Torque Off data
For full details of the Safe Torque Off (STO) function please refer to section 6.17
7.1.21 Input current, fuse and cable size ratings
The input current is affected by the supply voltage and impedance.
Typical input current
The values of typical input current are given to aid calculations for power flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses. These values are stated for the worst case
condition with the unusual combination of stiff supply with bad balance. The value stated for the maximum continuous input current would only be
seen in one of the input phases. The current in the other two phases would be significantly lower.
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence imbalance and rated at the maximum supply fault
current given in Table 7-20.
Table 7-20 Supply fault current used to calculate maximum input currents
Size
Dimension
H
W
D
F
R
9A
1108 mm (43.61 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
100 mm (3.94 in)
9E/10E
1069 mm (42.09 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
99 mm (3.90 in)
9T/10T
1159 mm (45.63 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
100 mm (3.94 in)
11E/T
1242 mm (48.9 in)
310 mm (12.21 in)
313 mm (12.32 in)
190 mm (7.48 in)
123 mm (4.84 in)
9D/10D
773 mm (30.43 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
100 mm (3.94 in)
11D
863 mm (33.97 in)
310 mm (12.21 in)
312 mm (12.28 in)
190 mm (7.48 in)
122 mm (4.8 in)
10 rectifier
355 mm (13.98 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
99 mm (3.90 in)
11 rectifier
405.5 mm (15.96 in)
310 mm (12.21 in)
290 mm (11.42 in)
190 mm (7.48 in)
100 mm (3.9
4
in)
Size
kg
lb
9E/10E
46
101.40
9T/10T
60
132.3
9D/10D
34
74.9
9A
66.5
146.6
10 rectifier
13
28.7
11E
63
138.9
11D
42
92.6
11T
65
143.3
Size 11 single rectifier
21
46.3
Size 11 twin rectifier
23
50.7
Model
Symmetrical fault level (kA)
All
100
Fuses
The AC supply to the drive must be installed with suitable protection against overload and short-circuits. Table 7-21 and Table 7-23 show
the recommended fuse ratings. Failure to observe this requirement will cause risk of fire.
WARNING