Figure 5-2: Low Alarm Logic
A. Chlorine, ppm
B. Alarm deactivates
C. Deadband = 0.3 ppm
D. Time
E. Alarm activates
F. Low alarm setpoint
The alarm activates when the chlorine concentration
drops below the low setpoint. The alarm remains
activated until the reading increases above the value
determined by the deadband.
Interval timer
Any alarm relay can be used as an interval timer.
the timer operates. While the interval timer is operating, the main
display, analog outputs, and assigned alarms for the sensor(s) can be put
on hold. During hold, the main display remains at the last value.
Programming the transmitter
Reference Manual
May 2019
00809-0100-3412
48