1
General information
1.1
Overview
The Rosemount
™
CX1100 In Situ Oxygen Transmitter provides a continuous, accurate
measurement of the oxygen remaining in flue gases coming from a combustion process.
Accurate measurements of furnace exhaust excess oxygen are critical for combustion
optimization, which result in reduced energy costs, increased safety, and lower emissions.
This product is intended for use for combustion applications only.
The Rosemount CX1100 probe contains a zirconia type oxygen sensor. At high
temperatures, zirconia produces an electrical potential that is proportional to the
difference in process oxygen concentration and ambient reference air. This voltage is
transmitted to the Rosemount CX1100 remote transmitter and output as an analog signal.
The sensor is mounted at the end of the probe tube which extends into a flue gas duct or
stack. Varying lengths of the probe are available to achieve desired insertion depths. The
probe tube also houses a heating element to precisely control the temperature of the
sensor, reducing errors induced by varying process temperatures.
1.2
Rosemount CX1100 Oxygen Probe and
Transmitter
A complete Rosemount CX1100 In Situ Oxygen Transmitter system includes a probe and
remote transmitter. Raw signals (sourced from the heater thermocouple and oxygen
sensor) and power are transmitted between the Rosemount CX1100 probe and the
Rosemount CX1000 remote transmitter, interconnect wiring consisting of nine
conductors. The specifications of the wiring arrangement can be found in
Chapter 3
. If
following the specifications, 200 ft (61 m) is the maximum cable length allowed.
General information
Reference Manual
1
Summary of Contents for Rosemount CX1100
Page 1: ...Reference Manual 00809 0100 4110 Rev AA June 2018 Rosemount CX1100 In Situ Oxygen Transmitter ...
Page 4: ......
Page 6: ...Contents ii Rosemount CX1100 ...
Page 18: ...Wall Surface and Pipe Mount Figure 2 4 Install 12 Rosemount CX1100 ...
Page 19: ...Panel Mount Figure 2 5 Install Reference Manual 13 ...
Page 20: ...Install 14 Rosemount CX1100 ...
Page 26: ...Wire 20 Rosemount CX1100 ...
Page 28: ...Startup 22 Rosemount CX1100 ...
Page 32: ...Calibration and maintenance 26 Rosemount CX1100 ...
Page 36: ...Rosemount CX1100 In Situ Oxygen Transmitter menu trees 30 Rosemount CX1100 ...
Page 45: ...Rosemount CX1100 product certifications Reference Manual 39 ...
Page 46: ...Rosemount CX1100 product certifications 40 Rosemount CX1100 ...
Page 47: ...Rosemount CX1100 product certifications Reference Manual 41 ...