Table 1-4: Sensitivity Range Levels
(continued)
Level
Response time (sec)
Sensitivity range - ft. (m) (for
1 ft.
2
(0.1 m
2
) n-heptane pan
fire)
3
8
150 (45)
4
10
215 (65)
For some typical ambient conditions, the Zeta parameter as defined in NFPA 72 for the
detector is 0.005 (1/meter).
Note
Zeta parameters may vary significantly with changes in temperature, air pressure,
humidity, visibility conditions, etc.
Other fuels
The detector reacts to other types of fire as follows:
•
The baseline fire refers to n-heptane 1 ft.
2
(0,1 m
2
) and is defined as 100 percent
sensitivity.
•
For fuel fire: standard pan fire size: 1 ft.
2
(0,1 m
2
)
•
For gas flame: 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
•
Maximum response time: 10 sec.
Table 1-5: Fuel Sensitivity Ranges
Type of fuel
Percent of max. distance at each sensitivity range
Max. distance
(ft. / m)
Gasoline
100%
215 / 65
n-Heptane
100%
215 / 65
JP5
70%
150 / 45
Kerosene
70%
150 / 45
Diesel fuel
70%
150 / 45
Ethanol 95%
60%
135 / 40
IPA
60%
135 / 40
Methanol
55%
115 / 35
Methane
70%
150 / 45
70%
150 / 45
Paper
38%
82 / 25
Polypropylene
55%
115 / 35
(1)
30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire
Reference Manual
Introduction
00809-0100-4975
August 2019
Rosemount 975MR