NOTICE
The item letters in this procedure can be found in
Procedure
1. Place the flame simulator in a safe area, not exceeding 104 °F (40 °C).
2. Release the locking screw.
3. Unscrew the battery back cover (D) counter-clockwise.
4. Unscrew the locking disc (C) clockwise.
5. Pull out the battery from the flame simulator.
6. Connect the battery to the charger.
7. Charge for a maximum of two to three hours.
8. Disconnect the charger.
9. Insert the battery in the flame simulator.
10. Screw on the locking disc (C).
11. Screw on the back cover (D).
12. Lock the back cover with the locking screw.
D.1.6
Replace the battery
NOTICE
The item letters shown in this procedure can be found in
.
Procedure
1. Place the flame simulator on a table in a safe area, not exceeding 104 °F (40 °C).
2. Release the locking screw.
3. Unscrew the battery back cover (D) counter-clockwise.
4. Unscrew the locking disk (C) clockwise.
5. Pull out the battery from the flame simulator.
6. Insert the new battery pack in the simulator housing.
Use only Rosemount battery pack, PN 00975-9000-0012.
7. Screw on the locking disc (C).
8. Screw on the back cover (D).
9. Lock the back cover with the locking screw.
NOTICE
For more information, refer to
.
Accessories
Reference Manual
August 2019
00809-0100-4975
64