2. Send the detector back for repairs.
4.2.3
Fault relay at N.O.
Yellow/amber LED flashes at 4 Hz.
0-20 mA at 2 mA
BIT fault: faulty detector
Recommended actions
1. Clean detector window.
2. Re-power the detector.
3. Replace the detector.
4.2.4
Red LED constantly on
If no fire exists, the detector alarm may be latched.
Recommended action
Reset the detector.
4.2.5
Alarm relay at on
0-20 mA at 20 mA
Alarm condition
Recommended actions
1. Check cause of alarm.
2. If no alarm, re-power the detector.
3. Send the detector back for repairs.