7
Specifications
7.1
Technical specifications
Spectral response
Rosemount 975MR
Four infrared (IR) bands between 4 μm and 5 μm
Rosemount 975HR
Four IR bands between 2 μm and 5 μm
Rosemount 975UF
Ultraviolet (UV): 0.185 - 0.260 μm
IR: 2.5-3.0 μm
Rosemount 975UR
UV: 0.185 - 0.260 μm
IR: 4.3 – 4.8μm
Detection range per fuel (ft./m)
Note
The ranges shown are at highest sensitivity setting for 1 ft
2
(0.1 m
2
) pan fire.
Table 7-1: Rosemount 975 Models
Fuel
Rosemount
975MR
Rosemount
975HR
Rosemount
975UF
Rosemount
975UR
Gasoline
300 ft (90 m)
93 ft (28 m)
N-Heptane
300 ft (90 m)
93 ft (28 m)
Diesel fuel
207 ft (63 m)
70 ft (21 m)
Kerosene
207 ft (63 m)
70 ft (21 m)
Alcohol 95%
185 ft (55 m)
57 ft (17 m)
Isopropyl alcohol
(IPA)
185 ft (55 m)
70 ft (21 m)
Methanol
185 ft (55 m)
57 ft (17 m)
Methane
207 ft (63 m)
60 ft (18 m)
Liquified
petroleum gas
(LPG)
207 ft (63 m)
60 ft (18 m)
Polypropylene
160 ft (49 m)
60 ft (18 m)
Paper
112 ft (34 m)
10 ft (3 m)
Hydrogen
N/A
164 ft (50 m)
70 ft (21 m)
N/A
Magnesium
alloy
N/A
33 ft (10 m)
Gun powder
197 ft (60 m)
66 ft (20 m)
93 ft (28 m)
Fireworks
33 ft (10 m)
10 ft (3 m)
Reference Manual
Specifications
00809-1400-4975
February 2022
Rosemount 975
31
Summary of Contents for Rosemount 975 Series
Page 1: ...Reference Manual 00809 1400 4975 Rev AB February 2022 Rosemount 975 Flame Detectors ...
Page 22: ...Installation Reference Manual February 2022 00809 1400 4975 22 Emerson com Rosemount ...
Page 28: ...Maintenance Reference Manual February 2022 00809 1400 4975 28 Emerson com Rosemount ...
Page 36: ...Specifications Reference Manual February 2022 00809 1400 4975 36 Emerson com Rosemount ...
Page 38: ...Reference data Reference Manual February 2022 00809 1400 4975 38 Emerson com Rosemount ...
Page 43: ...Reference Manual 00809 1400 4975 February 2022 Rosemount 975 43 ...