Electrical input
protection
According to EN 50130
Electromagnetic
capability
Electromagnetic interference/Radio frequency interference
(EMI/RFI) protected to EN61000-6-3 and EN 50130
Electrical interface
The detector includes 17 terminals, one wiring option.
Electrical input protection
The input circuit is protected against voltage-reversed polarity, voltage transients, surges,
and spikes according to EN 54-10.
Outputs
Relays
Alarm, fault, and auxiliary
SPST volt-free contacts rated 2A at 30 Vdc
Analog
5 V at detection, 0 V at fault, 2 V at normal
0-20 mA
(stepped)
Fault: 0 +1 mA
Built-in test (BIT) Fault: 2 mA ± 0.3 mA
Normal: 4 mA ± 0.3 mA
Warning: 16 mA ± 0.3 mA
Alarm: 20 mA ± 0.3 mA
Heated optics
The front window can be heated to improve performance in ice, condensation, and snow
conditions. The heater increases the temperature of the optical surface by 5 °C to 25 °C
above the ambient temperature
. The heated optics can be configured in three ways:
Off
Optics are not heated
On
Optics are continuously heated
Auto (default)
Operated only when the change of temperature requires the heating
Note
In Auto mode, the starting heat temperature can be defined between 32 °F (0 °C) and 95 °F
(35 °C). The detector stops heating the window when the temperature is 15 °C above the
start temperature.
7.3
Mechanical specifications
Enclosure options
Stainless steel 316 with electropolish finish
Heavy duty copper free aluminum (less than one percent), polyurethane painted
(1)
Rosemount 975 flame detectors also have a low power heater option.
Specifications
Reference Manual
February 2022
00809-1400-4975
34
Emerson.com/Rosemount
Summary of Contents for Rosemount 975 Series
Page 1: ...Reference Manual 00809 1400 4975 Rev AB February 2022 Rosemount 975 Flame Detectors ...
Page 22: ...Installation Reference Manual February 2022 00809 1400 4975 22 Emerson com Rosemount ...
Page 28: ...Maintenance Reference Manual February 2022 00809 1400 4975 28 Emerson com Rosemount ...
Page 36: ...Specifications Reference Manual February 2022 00809 1400 4975 36 Emerson com Rosemount ...
Page 38: ...Reference data Reference Manual February 2022 00809 1400 4975 38 Emerson com Rosemount ...
Page 43: ...Reference Manual 00809 1400 4975 February 2022 Rosemount 975 43 ...