Sensitivity ranges
Note
All distances relate to detection of a 1 ft
2
(0.1 m
2
) n-heptane fire.
Table 7-5: Rosemount 975 Models
Rosemount 975MR
Rosemount 975HR
Rosemount 975UF
Rosemount 975UR
Six ranges:
•
10 ft (3 m)
•
50 ft (15 m)
•
100 ft (30 m)
•
150 ft (45 m)
•
215 ft (65 m)
•
300 ft (90 m)
Three ranges:
•
10 ft (3 m)
•
50 ft (15 m)
•
92 ft (28 m)
Field of view
Table 7-6: Rosemount 975 Models
Rosemount 975MR
Rosemount 975HR
Rosemount 975UF
Rosemount 975UR
Horizontal: 100°
Vertical: 95°
Hydrogen
Horizontal: 90°
Vertical: 90°
Horizontal: 100°
Vertical: 95°
Other fuels
Horizontal: 80°
Vertical: 80°
Temperature range (operating and storage)
Table 7-7: Rosemount 975 Models
Rosemount 975MR
Rosemount 975HR
Rosemount 975UF
Rosemount 975UR
-76 °F (-60 °C) to 185 °F (85 °C)
Humidity
Non-condensing relative humidity up to 100 percent.
7.2
Electrical specifications
The electrical specifications apply to all models unless stated otherwise.
Operating voltage
24 Vdc nominal (18-32 Vdc)
Power consumption
Standby: Max. 3 W (8 W with heated window)
Alarm: Max. 4.2 W (9.6 W with heated window)
Cable entries
2 x
¾
-in - 14 NPT conduits or 2 x M25 x 1.5 mm International
Organization for Standardization (ISO)
Reference Manual
Specifications
00809-1400-4975
February 2022
Rosemount 975
33
Summary of Contents for Rosemount 975 Series
Page 1: ...Reference Manual 00809 1400 4975 Rev AB February 2022 Rosemount 975 Flame Detectors ...
Page 22: ...Installation Reference Manual February 2022 00809 1400 4975 22 Emerson com Rosemount ...
Page 28: ...Maintenance Reference Manual February 2022 00809 1400 4975 28 Emerson com Rosemount ...
Page 36: ...Specifications Reference Manual February 2022 00809 1400 4975 36 Emerson com Rosemount ...
Page 38: ...Reference data Reference Manual February 2022 00809 1400 4975 38 Emerson com Rosemount ...
Page 43: ...Reference Manual 00809 1400 4975 February 2022 Rosemount 975 43 ...