The detector can be set to perform the BIT in the following modes:
•
Automatically and manually
•
Manually only
BIT operation
The BIT is intended to check optical integrity and electronic circuitry. The detector's status
remains unchanged if the result of a BIT is the same as the current status (Normal or BIT
Fault). The detector’s status changes if the BIT differs from the current status.
Note
In BIT Fault status, the detector can continue to detect a fire in most cases.
Automatic BIT
The detector automatically performs a BIT every 15 minutes. A successful BIT sequence
does not activate any indicator. If required, you can modify the automatic BIT interval
using the RS-485 Modbus
®
Manager or HART
®
communicator. In case of a BIT fault, this
sequence continues until a successful BIT occurs, when the detector resumes normal
operation.
•
As the result of a
successful
automatic/manual BIT, the fault relay remains
energized
.
•
As the result of an
unsuccessful
automatic/manual BIT (which occurs after three
failures), the fault relay
de-energizes
.
Manual BIT
You can initiate manual BIT using the Modbus Manager or HART communicator or by
connecting terminal
3
to ground. You can also use the Modbus Manager or HART
communicator to configure the manual BIT's alarm duration.
Initial setup
Reference Manual
February 2022
00809-1400-4975
26
Emerson.com/Rosemount
Summary of Contents for Rosemount 975 Series
Page 1: ...Reference Manual 00809 1400 4975 Rev AB February 2022 Rosemount 975 Flame Detectors ...
Page 22: ...Installation Reference Manual February 2022 00809 1400 4975 22 Emerson com Rosemount ...
Page 28: ...Maintenance Reference Manual February 2022 00809 1400 4975 28 Emerson com Rosemount ...
Page 36: ...Specifications Reference Manual February 2022 00809 1400 4975 36 Emerson com Rosemount ...
Page 38: ...Reference data Reference Manual February 2022 00809 1400 4975 38 Emerson com Rosemount ...
Page 43: ...Reference Manual 00809 1400 4975 February 2022 Rosemount 975 43 ...