DD is required. To obtain the latest DD, visit the Emerson Easy Upgrade site at:
Emerson.com/Rosemount/Device-Install-Kits
.
Figure 4-2: AMS Device Manager
Note
SteamLogic
™
software is provided for viewing steam trap status. Refer to the manual on
the CD for more information.
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of
the network ID and join key, and that Active Advertising has been enabled on the Gateway.
The network ID and join key in the device must match the network ID and join key of the
Gateway.
The network ID and join key may be obtained from the Gateway on the System
Settings>Network> Network Settings page of the web server (see
ID and join key may be changed in the wireless device by following the Fast Key sequence
shown below.
Function
Key sequence
Menu items
Join Device to Network
2, 1, 2
Network ID, Set Join Key
Reference Manual
Commissioning
00809-0100-4708
June 2022
Rosemount 708 Wireless Acoustic Transmitter Reference Manual
23