Figure 3-3: Connection
COMM
P/N 00753-9200-0020
1
2
3
4
3.4
Physical installation
3.4.1
Transmitter installation
The transmitter can be installed in one of two configurations:
•
Direct Mount, where the sensor is connected directly to the Rosemount 648 Wireless
housing’s conduit entry.
•
Remote Mount, where the sensor is mounted separate from the Rosemount 648
Wireless housing, then connected to the transmitter using conduit.
Select the installation sequence that corresponds to the mounting configuration.
3.4.2
Direct mount
The direct mount installation should not be used when installing with a Swagelok
®
fitting.
Procedure
1. Install sensor according to standard installation practices using approved thread
sealant on all connections.
2. Attach transmitter housing to the sensor using the threaded conduit entry.
3. Attach sensor wiring to the terminals as indicated on the wiring diagram.
4. Connect Black Power Module.
Note
Wireless devices should be powered up in order of proximity from the Wireless
Gateway, beginning with the closest device to the gateway. This will result in a
simpler and faster network installation.
Installation
Reference Manual
May 2020
00809-0200-4648
36
Rosemount 648 Wireless
Summary of Contents for Rosemount 648
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0200 4648 8 Rosemount 648 Wireless ...
Page 32: ...Configuration Reference Manual May 2020 00809 0200 4648 32 Rosemount 648 Wireless ...
Page 48: ...Commissioning Reference Manual May 2020 00809 0200 4648 48 Rosemount 648 Wireless ...
Page 58: ...Operation and maintenance Reference Manual May 2020 00809 0200 4648 58 Rosemount 648 Wireless ...
Page 66: ...Troubleshooting Reference Manual May 2020 00809 0200 4648 66 Rosemount 648 Wireless ...
Page 68: ...Reference data Reference Manual May 2020 00809 0200 4648 68 Rosemount 648 Wireless ...