Figure 2-18: Example 2: Falling Alert
Deadband
Assigned Value
Alert Set Point
Alert “OFF”
Alert “ON”
Alert “OFF”
U
n
it
s
o
f
Me
a
su
re
me
n
t
Time
Field Communicator
To configure the process alerts with a Field Communicator, perform the following
procedure:
Procedure
1. From the
HOME
screen, follow the Fast Key sequence,
2 Configure
→
1 Guided
Setup
→
1 Guided Setup
.
2. Select
2 for Hi-Hi Alarm
, or Select
3 for Hi Alarm
, or Select
4 for LO Alarm
, or
Select
5 for LO-LO Alarm
and press
Enter
.
3. If the alarm is disabled, select
1 Enable
and press
Enter
. If the alarm was previously
enabled, select
2 Leave Enabled
and press
Enter
.
4. Enter the alarm limit and press
Enter
.
5. Enter the alarm deadband and press
Enter
.
2.10
Remove power module
After the sensor and network have been configured, remove the Power Module and
replace the transmitter cover. The Power Module should be inserted only when the device
is ready to be commissioned. Use caution when handling the Power Module. The Power
Module may be damaged if dropped from heights in excess of 20 feet.
Reference Manual
Configuration
00809-0200-4648
May 2020
Rosemount 648 Wireless
31
Summary of Contents for Rosemount 648
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0200 4648 8 Rosemount 648 Wireless ...
Page 32: ...Configuration Reference Manual May 2020 00809 0200 4648 32 Rosemount 648 Wireless ...
Page 48: ...Commissioning Reference Manual May 2020 00809 0200 4648 48 Rosemount 648 Wireless ...
Page 58: ...Operation and maintenance Reference Manual May 2020 00809 0200 4648 58 Rosemount 648 Wireless ...
Page 66: ...Troubleshooting Reference Manual May 2020 00809 0200 4648 66 Rosemount 648 Wireless ...
Page 68: ...Reference data Reference Manual May 2020 00809 0200 4648 68 Rosemount 648 Wireless ...