25
Reference Manual
00809-0100-4570, Rev DA
Electrical Installation
November 2017
Electrical Installation
Using the Rosemount 3DVision to communicate with the units allow the user to choose one of several
communication types: RS-485, GSM, GPRS or TCP/IP, for more information and details regarding the
communications, refer to the
“Communication methods” on page 91
Wire the Rosemount 5708
1. Verify the power supply is disconnected.
2. Loosen the compression nut of the cable gland entry.
3. Insert the cable through the cable gland entry.
Always observe the following safety instructions:
Connections must be made only in the complete absence of line voltage.
If over-voltage is expected, overvoltage arresters should be installed.
Use only a safety-certified power supply with dual insulation between the primary and output for
powering the unit. The power supply output rating must be limited to 18-32 Vdc, 1 A for a single
Rosemount 5708, and not to be connected to a DC distribution network.
The 4-20mA lines should NOT be connected in multi-drop.
Summary of Contents for Rosemount 5708
Page 1: ...Reference Manual 00809 0100 4570 Rev DA November 2017 Rosemount 5708 3D Solids Scanner ...
Page 2: ...ii Section Title November 2017 Reference Manual 00809 0100 4570 Rev DA ...
Page 8: ...vi Reference Manual 00809 0100 4570 Rev DA Contents November 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0100 4570 Rev DA Introduction November 2017 Introduction ...
Page 202: ...ii Reference Manual 00809 0100 4570 Rev DA Index November 2017 Index ...
Page 203: ...iii Reference Manual 00809 0100 4570 Rev DA November 2017 ...