Section 9: Alarm Relay Functions
Instruction Manual
April 2017
LIQ-MAN-56
70
Alarm Relay Functions
* See Appendix 1 – HART and Device Variables
9.4
Bleed and Feed
9.4.1
Description:
A bleed and feed timer is typically used to replace chemicals lost during blowdown. It
involves two or more relays. The bleed relay is a normal setpoint alarm relay. Once the bleed
relay deactivates, one or more feed relays activate for a percentage of the time the bleed
relay was on.
Bleed and Feed supports continuous monitoring of blow-down water conductivity to
determine the point of excessive conductivity. At a programmable maximum concentration
value, dumping (bleeding) of the excessively dirty blow-down water is triggered.
Subsequently, pumping (feeding) of additional make-up water chemicals is enabled to
account for lost blow-down water. Through level control, make-up water is added in
proportion to the volume of blowdown material lost through dumping and evaporation.
A schematic of the Bleed and Feed timer operation is shown:
9.4.2
Setup
Access Bleed and Feed Timers by pressing ENTER/MENU from the main screen and then
Program/Relays/Configure Relay. From the main relay programming screen, program this
feature as follows:
1.
Relay:
Assign relay 1 for Bleed and Feed and press ENTER/MENU.
2.
Type:
Select Bleed and Feed as the relay type and press ENTER/MENU.
3.
Assign:
Assign S1 (sensor 1), S2 (sensor 2 if available) or other available parameters to
the designated relay and press ENTER/MENU.
4.
Logic:
Set High for high setpoint or Low for low setpoint and press ENTER/MENU.
Relay Function
Limits and Selections
Default
Delay Timer
NA
NA
Logic
Low/High
High
Setpoint
*
*
Deadband
*
0.000
Normal state
Close/Open
Open
Table 9-3. Defaults and programmable limits
Figure 9-3. Bleed and feed timer alarm operation
time
bleed on
on
off
AL1
(bleed)
AL2
(feed)
feed on
delay
feed time = X% of bleed time
Summary of Contents for Rosemount 56
Page 1: ...Instruction Manual LIQ MAN 56 Rev D April 2017 Rosemount 56 Advanced Dual Input Analyzer ...
Page 2: ......
Page 10: ...iv Table of Contents Instruction Manual April 2017 LIQ MAN 56 ...
Page 30: ...Section 2 Installation Instruction Manual April 2017 LIQ MAN 56 20 Installation ...
Page 40: ...30 Wiring Section 3 Wiring Instruction Manual April 2017 LIQ MAN 56 ...
Page 64: ...Section 6 Programming Measurements Instruction Manual April 2017 LIQ MAN 56 54 ...
Page 76: ...Section 8 Time Proportional Control Instruction Manual April 2017 LIQ MAN 56 66 ...
Page 124: ...Section 13 Maintenance Instruction Manual April 2017 LIQ MAN 56 114 ...
Page 126: ...Section 14 Return of Material Instruction Manual April 2017 LIQ MAN 56 116 ...