Section 8.0 Time Proportional Control
8.1
Introduction
8.1.1
Time Proportional Control
Time Proportional Control is more commonly known as Duty Cycle or Pulse Width Modulation.
It applies PID control to the activation of a relay rather than using an analog output.
The TPC output is defined as the percent of time that a relay is on (% On Time), during a user
selected time period (Time Period). As the control output increases the on time increases:
The proportional, integral, and derivative are defined the same as analog PID control, but
use % On Time instead of % Output:
Proportional On Time (%) = [Gain
×
(PV – SP) x 100 / (URV – LRV)] + BIAS
Proportional and Integral Control:
% On Time = [Gain
×
100 / (URV – LRV)] + [(PV – SP) + 1/I
Σ
(PV
t
– SP)
Δ
t]
Derivative Mode:
% On Time = [Gain
×
100 / (URV – LRV)]
×
D
×
[(PV
t
– SP)
−
(PV
t-1
– SP)] /
Δ
t
As with analog PID control, TPC can be direct acting (URV > LRV) or reverse acting (LRV >
URV). For more detail see Section X.1, PID Control Introduction.
Fig. 8-1 TPC Periods and On Time
Summary of Contents for Rosemount 56
Page 1: ...Instruction Manual LIQ MAN 56 Rev D April 2017 Rosemount 56 Advanced Dual Input Analyzer ...
Page 2: ......
Page 10: ...iv Table of Contents Instruction Manual April 2017 LIQ MAN 56 ...
Page 30: ...Section 2 Installation Instruction Manual April 2017 LIQ MAN 56 20 Installation ...
Page 40: ...30 Wiring Section 3 Wiring Instruction Manual April 2017 LIQ MAN 56 ...
Page 64: ...Section 6 Programming Measurements Instruction Manual April 2017 LIQ MAN 56 54 ...
Page 76: ...Section 8 Time Proportional Control Instruction Manual April 2017 LIQ MAN 56 66 ...
Page 124: ...Section 13 Maintenance Instruction Manual April 2017 LIQ MAN 56 114 ...
Page 126: ...Section 14 Return of Material Instruction Manual April 2017 LIQ MAN 56 116 ...