Emerson PMAC II Solo Installation And Operation Manual Download Page 1

Pulse Modulating and Anti-Sweat 
Control (PMAC II Solo) Installation and  
Operation Manual

026-1503 Rev 0

Summary of Contents for PMAC II Solo

Page 1: ...Pulse Modulating and Anti Sweat Control PMAC II Solo Installation and Operation Manual 026 1503 Rev 0 ...

Page 2: ......

Page 3: ...uite 100 Kennesaw GA 30144 USA Phone 770 425 2724 Fax 770 425 9319 Please Note This manual covers only the PMAC II Solo P N 851 1104 model If information is needed on the PMAC II network version consult the PMAC II manual P N 026 1501 ...

Page 4: ......

Page 5: ...O PANEL 4 1 5 1 Keypad 4 1 5 2 How the Setpoints Work 4 1 5 3 Logging Into the UC12PG R 4 1 5 4 Entering Changing Setpoints 5 1 5 4 1 Setting Time Date 5 1 5 4 2 Setting Dewpoints 6 1 5 4 3 Setting Pulse Percentages 6 1 5 4 4 Setting Load Shed 7 1 5 4 5 Setting Temperature and RH Offsets 7 1 5 4 6 Setting the Sensor Fail Output 7 1 5 5 Alarms 8 1 5 5 1 Navigating the Alarm Screens 8 1 5 5 2 Viewin...

Page 6: ......

Page 7: ...el to control of all anti sweat heaters channels based on dewpoint calculated from relative humidity and temperature inputs without need for a central CPC site control system The UC12PG R does not support multiple zone control All heaters are controlled by the same setpoint and dew point inputs 1 1 Features Full Solid State Control Quiet Operation Easily added to existing systems Controlled by the...

Page 8: ...rom doors windows vents heaters and outside walls that could affect temperature readings The sensor should be be tween four and six feet from the floor In addition the sen sor should not be mounted above other sensors that generate heat during operation such as relative humidity sensors To mount the sensor use a screwdriver to press in the tab on the left side of the sensor enclosure and lift the ...

Page 9: ...II Solo panel The necessary connections between this terminal strip and the UC12PG R controller are hard wired by CPC during man ufacturing 1 3 2 1 Wiring for RH Sensor 1 3 2 2 Sensor Cable Type Wire the sensors to the PMAC II Solo terminal strip us ing Belden 8641 or equivalent for the temperature sensor and Belden 8771 or equivalent for the humidity sensor 1 3 2 3 Wire Connections Figure 1 9 sho...

Page 10: ... Dewpoint setpoint the heaters will op erate at the percentage specified in the Minimum Pulse Percentage setpoint When the dewpoint is between the minimum and maximum setpoint the PMAC II Solo s pulse percentage varies between the Minimum Pulse Per centage and 100 the higher the dewpoint the higher the pulse percentage Finally if the dewpoint meets or ex ceeds the Maximum Dewpoint setpoint the hea...

Page 11: ...to 1 SET TIME AND DATE and press the button to select Use the or buttons to access all the date and time values in the Date and Time Configuration screen Figure 1 15 2 Press the or buttons to move the cur sor to the month field of the current date Use the and buttons to set the month 01 12 3 Press the or buttons to move the cur sor to the days field of the current date Use the and buttons to set t...

Page 12: ...e button to select 10 Use the or buttons to adjust the set point to the desired minimum dewpoint level 11 Press the button to save changes and go back to the Configuration screen 12 Use the or buttons to select 3 SET MAX DEWPOINT and use the and buttons to adjust the setpoint to the desired maximum dewpoint level 13 Press the button to save changes and go back to the Setpoints Configuration screen...

Page 13: ...n to save and go back to the Config uration screen 18 From the Configuration screen press the button to scroll down the list to 8 SET RH OFFSET and press the button to select Use the and buttons to add or sub tract an offset from the humidity sensor read ing Press the button to save and go back to the Configuration screen 1 5 4 6 Setting the Sensor Fail Output Setting the Sensor Fail Output is the...

Page 14: ...w any text that is not visi ble on screen 1 5 5 2 Viewing the Alarm Screens 3 View an alarm by using the and but tons to choose an alarm from the alarm log list Press the button to select and view The alarm screen Figure 1 27 shows the number the alarm appears in the log the name of the alarm the time and date it was recorded and the alarm status Active or Cleared 4 Once an alarm has been viewed a...

Page 15: ...oller to reboot 1 5 6 Percentage On Times Percent On Time shows the average duty cycle on time that the anti sweat outputs have been operating at For example if the outputs have operated at 0 for half an hour and 100 for the next half hour the Hour Percent On Time would show 50 Setting Zero On Time to Active manually resets all calculations 1 5 6 1 Viewing the Percentage On Time Screens 1 Log into...

Page 16: ...en press the button to move the cursor to 4 ON LAST MONTH and press the button to select and view The Average Output for Month gives the average run time percentage of the outputs for every month The calcu lation starts at midnight on the first day of each month and is restarts at the beginning of each month 10 The screen displays the average output per centage for the most recent week of opera ti...

Page 17: ... move the cursor to 2 VIEW SPACE TEMP and press the button to select and view This screen displays the current space temperature 6 Press the or button to go back to the Status View screen 7 From the Status View screen press the button to move the cursor to 3 VIEW DEW POINT and press the button to select and view This screen displays the current inside dewpoint tem perature 8 Press the or button to...

Page 18: ... screen 15 From the Status View screen press the button to move the cursor to 7 VIEW MAX PULSE and press the button to select and view This screen displays the maximum pulse rate generated at the maximum dewpoint setpoint 16 Press the or button to go back to the Status View screen 17 From the Status View screen press the button to move the cursor to 8 VIEW LOAD SHED and press the button to select ...

Page 19: ...0 SOFTWARE STATUS and press the button to select and view This screen displays the version of the software 22 Press the button to go back to first Status View screen Figure 1 39 or the button to go back to the last Status View screen you were on 23 Press the button once to go back to the Main Configuration screen Figure 1 12 and twice to go back to the default home screen Figure 1 49 Load Shed Pul...

Page 20: ...Programming the UC12PG R Controller on the PMAC II Solo Panel Overview 14 ...

Page 21: ......

Page 22: ... Climate Technologies Retail Solutions Inc and or its affiliates collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 02...