58 • MultiFlex CUB-II and CUB-TD I&O Guide
026-1705 Rev 7 06-APR-2010
8.2.8. Outputs Screens
The two screens under the heading “Output”
are where you assign each of the eight relay out-
puts to a controlled device in the condensing unit
system.
8.2.9. Auxiliary Inputs Screens
8.2.9.1.
Pulse KW Setup
KW Per Pulse
If you are using a pulse accumulation type
KW transducer, you must enter the number of
KW per pulse for this transducer in this field.
8.2.9.2.
Analog KW Setup
KW Analog
If you are using an analog KW transducer,
you must enter the voltage range of the input and
the range of KW values the voltage corresponds
to. This information is different for each KW
Transducer and depends on the line voltage and
current transducer (CT) rating. Refer to your
KW transducer’s installation instructions.
Under the
Volts
column, enter the minimum
and maximum sensor output voltages. Under the
KW
column, enter the minimum and maximum
KW represented by the min/max voltage range.
8.2.9.3.
Linear 1 and 2 Setup
Linear 1 and 2
If you wish to use one or both of the Linear 1
and Linear 2 sensor types used by the sensor
control applications, you must specify the volt-
age range of the sensor output and the range of
values those voltages represent.
Under the
Volts
column, enter the minimum
and maximum sensor output voltages. Under the
Output
column, enter the minimum and maxi-
mum engineering unit values represented by the
min/max voltage range.
Sensor Control
Input Type
Description
Comp
The compressor
CondFan1
Condenser fan #1
CondFan2
Condenser fan #2
CondFan3
Condenser fan #3
CondFan4
Condenser fan #4
Defrost
The defrost output
Refr Sol
Refrigeration solenoid
Evap Fan
Case evaporator fan
Alarm
The alarm output (turns ON when
alarm condition exists on CUB)
SensCtrl1
Output controlled by sensor control
loop #1
SensCtrl2
Output controlled by sensor control
loop #2
Remote
Unused by CUB, but may be con-
trolled by E2 or Einstein remotely
NDF
Not defined
Table 8-4 - CUB Sensor Control Output Types
Out #1 Comp
Out #2 Defrost
Out #3 CondFan1
Out #4 Remote
Out #5 Remote
Out #6 Remote
Out #7 Remote
Out #8 Alarm
Pulse KW Setup
KWH per
Pulse: 20
Analog KW Setup
Volts KW
Min: 0 0
Max: 5 5000
Linear 1 Setup
Volts Output
Min: 0 0
Max: 5 100
Linear 2 Setup
Volts Output
Min: 0 0
Max: 5 1000