Altering CUB Configuration Using The Hand-Held Terminal
The MultiFlex CUB Hand-Held Interface • 57
Type
The
Type
field tells the CUB what kind of
sensor is providing the input value. This value of
this field must correspond to the type of input
suggested by the
Name
field. For example, if the
Name of an input is Suct Temp, CaseTemp1, or
one of the other analog temperature sensor types,
the
Type
field must be set to
TEMP
in order for
the input signal from the sensor to be read like a
temperature sensor.
Note that when you choose a value for the
Name
field, the CUB does not automatically
enter an appropriate default value in the
Type
field. You must manually enter the type for all
sensor inputs.
Table 8-3
lists the input types available for
sensor control inputs.
Name
Description
Suct Xdcr
Suction pressure transducer
Disch Xdcr
Discharge pressure transducer
Oil Xdcr
Analog oil pressure transducer
Case 1 Temp-Case 6
Temp
Case temperature sensors #1 through
#6
DrLeg Temp
Drop Leg temperature sensor
Term Temp
Analog termination temperature sen-
sor (NOT digital — use Defrost Term
Sensor for digital sensors)
Term Dig
Digital defrost termination sensor
(NOT analog — Use Term Temp for
analog termination sensors)
Alarm Reset
Alarm reset button or switch
Door Switch
Door switch
Clean Switch
Clean switch
Disch Temp
Discharge temperature
SensCtrl 1-2
Input for Sensor Control modules #1
through #2
Comp Proof
Compressor proof
Phase Loss
Phase loss checking device
KW
Analog KW transducer input
Suct Temp
Suction Temperature probe
Oil Dig
Digital oil pressure switch
NOT USED
Input value is unused
Table 8-2 - MultiFlex CUB Input Names
NOTE: You may choose to have multiple in-
puts assigned to the same Sensor Control
module. These inputs will be combined by the
CUB-II’s sensor control application using the strategy
chosen in Sensor Control.
Input Type
Description
Temperature
Analog temperature sensor
12v-100PSI
12v transducer, 0-100PSI
12v-200PSI
12v transducer, 0-200PSI
12v-500PSI
12v transducer, 0-500PSI
5v-100PSI
5v transducer, 0-100PSI
5v-200PSI
5v transducer, 0-200PSI
5v-500PSI
5v transducer, 0-500PSI
Humidity
Relative Humidity Sensor
Power-KW
Kilowatt transducer, 1-5VDC analog
output signal
Ref Leak
Refrigerant Leak Detector
Dewpoint
Dewpoint Probe
LM235-TEMP
LM235 Temp Probe
Ref Level
Refrigerant Level Transducer
Liq Level
Liquid Level Transducer
Light Level
Light Level Sensor
Pulse-Cnt
Kilowatt transducer, pulse KW out-
put signal
Dig-ON/OFF
Digital ON/OFF signal
Linear-V
0-5 V linear sensor
Table 8-3 - CUB Sensor Control Input Types