60 Chapter 5 iCOM Controller
Liebert.PEX2 Series Air Conditioner User Manual
Parameters
Default Setting range
Description
S331
H DRAIN
-
On, Off
Humidfier drain
S332
HUM.C.
0.00A
-
Electric current of humidifier
S335
ALM REL
Off
On, Off
Diagnostic switch of alarm relay.
S336
K11 REL
-
On, Off
Diagnostic switch of free cooling relay.
S337 3P1
OPEN Off
On,
Off
S337 3P2
OPEN Off
On,
Off
S338 3P1
CLOSE Off
On,
Off
Diagnostic switch of 3-phase electric regulator.
S338 3P2
CLOSE Off
On,
Off
S339
BV CTRL
-
Man, Auto
Ball valve control type
S340
MBV1 POS
-
0 ~ 100%
S340
MBV2 POS
-
0 ~ 100%
MBV1 position, MBV2 position
S341
ANALOG1
0%
0 ~ 100%
S342
ANALOG2
0%
0 ~ 100%
S343
ANALOG3
0%
0 ~ 100%
Group 1
S344
ANALOG4
0%
0 ~ 100%
Diagnostic output of analog variable 1 ~ 4. They can be set to
be percentage of desired output
S345
RSD
On
On, Off
Remote shut down. Range: On, Off
S346
AIR LOSS
OK
OK, ACT
Air loss alarm. OK means the system is normal. ACT means
the air loss is active, and abnormity occurred
S347 MOTOR
OL ACT OK,
ACT
Fan motor overload alarm. OK means the fan is normal. ACT
means the fan is overloaded, and abnormality occurred
S348 FILTER
OK
OK,
ACT
Filter clogging situation. OK means normal; ACT means the
filter is clogged
S349 CUSTOM1 OK
OK,
ACT
S350 CUSTOM2 OK
OK,
ACT
S351
CUSTOM3
Ok
OK, ACT
S352 CUSTOM4 OK
OK,
ACT
States of customized alarms 1 ~ 4. ‘OK ‘means normality;
‘ACT’ means that the alarm is active and that abnormality
occurs
S353
HEAT SAF
OK
OK, ACT
Status heaters safety
S354 FLOW
AT %
-
-
S355 FLOW
ACT %
-
-
S356 HP1
OK
OK,
ACT
State of high pressure switch 1. OK means normal. ACT
means abnormal
S357 LP1
OK
OK,
ACT
State of low pressure switch 1. OK means normal. ACT
means abnormal
S358
C1 OL
OK
OK, ACT
Overload state of compressor 1. OK means normal. ACT
means abnormal
S359 HP2
OK
OK,
ACT
State of high pressure switch 2. OK means normal. ACT
means abnormal
S360 LP2
OK
OK,
ACT
State of low pressure switch 2. OK means normal. ACT
means abnormal
S361
C2 OL
OK
OK, ACT
Overload state of compressor 2. OK means normal. ACT
means abnormal
S367
HUM PROB
OK
OK, ACT
Humidifer fault state. OK means normal. ACT means
abnormal
S368
DT1
-
OK, ACT
Status DT1 (Outdoor/Glycol)
S369
DT2
-
OK, ACT
Status DT2 (Glycol/Room)
S370
DT3
On
On, Off
Status DT3 (Room/Setpoint)
S371
MIN CW
-
OK, ACT
Status Min CW
S372 LWD
Val
-
-
-
S374 LSI
-
-
-
S375 COND
2
-
-
-
S376 COND
1
-
-
-
S379
V_CTRL
Time
Time, Feedb
Valve Control
S380
V_CAL
No
Yes. No
Start Valve Calibration
S381 CAL_STAT Idle
-
-
S382 CLSD
1
-
-
-
S383 OPEN
1
-
-
-
S384 V1FDB
-
-
-
S385 CLSD
2
-
-
-
S386 OPEN
2
-
-
-
Group 2
S387 V2FDB
-
-
-