Chapter 5 iCOM Controller 61
5.7.6 SET ALARMS
The SET ALARMS menu is displayed in nine pages. The first page provides the settings of alarm upper/lower limits
and customized alarms. The other eight pages provide the settings of alarm delay.
Alarm upper/lower limits setting
The alarm upper/lower limits in the SERVICE MENUS are set the same as those in the USER MENUS. For details,
see Table 5-6
.
Customized alarms setting
See Table 5-23 for the descriptions of customized alarms setting.
Table 5-23 Descriptions of customized alarms setting
Parameters Default
Parameters Default
S202
RTN SNSR
Yes
S215
LO SUP
10°C
S203
HI TEMP
°C
S224
CUST IN1
WATER
S204
LO TEMP
°C
S225
C1 ACT
CLOSE
S205
HI HUM
60%
S226
CUST IN2
WATER
S206
LOW HUM
40%
S227
C2 ACT
CLOSE
S207
SENSOR A
No
S228
CUST IN3
WATER
S208
HI TEMP A
°C
S229
C3 ACT
CLOSE
S209
LO TEMP A
°C
S230
CUST IN4
HEAT A
S210
HI HUM A
%
S231
C4 ACT
OPEN
S211
LO HUM A
%
S232
WA AC AL
No
S213
SUP SNSR
No
S233
WAT OFF
No
S214
HI SUP T
24°C
CUST IN1, CUST IN2, CUST IN3 and CUST IN4 can be set to 21 types of input. See Table 5-24 for details.
Table 5-24 Descriptions of types
Types
Description
Types
Description
Types
Description
SMOKE
Smoke alarm
RH+HU
Rht + Hum lockout
RJTVS
HTRJ TVSS
WATER
Water leakage alarm
COMP
Compressor lockout
Fire
Fire Alarm
C PMP
Cooling pump alarm
Call
Call for service
2.Set
2nd Setpoint
FLOW
Insufficient water alarm
Temp
High temperature alarm
NoP
No Power
G PMP
Standby pump alarm
Air
Air loss alarm
LSI
LSI
STBY
Standby unit alarm
FC L.
FC lockout
Cnd 1
Condensor 1 Fail
C-In1
Customized alarm 1
HeatA
Heater alarm
Cnd 2
Condensor 2 Fail
C-In2
Customized alarm 2
FLOSD
Flow AL SD
ScRed
D-Scroll Red
C-In3
Customized alarm 3
FLOLC
Flow AL LC
Swap V
Swap Valve
C-In4
Customized alarm 4
ComPD
Comp Lock PD
ECFan
EC Fan Fail
RHT
Reheater lockout
En FC
Enable FC,
HUM Humidifier
lockout
RJVFD HTRJ
VFD
C1 ACT, C2 ACT, C3 ACT and C4 ACT correspond to the customer alarms. ‘OPEN’ means normally open, ‘CLOSE’
means normally closed.
Alarm delays setting
The alarm delays are the time after faults occur and before the alarms are triggered. See Figure 5-9 for the menu
format.
2/10
S236
S237
S238
S239
S240
S241
FOL
LOA
CF
HRT
LRT
HRH
DEL
EN
T
5
3
2
30
30
30
Yes
Yes
Yes
Yes
Yes
Yes
ALM
ALM
WRN
WRN
WRN
WRN
01
SET ALARMS
Figure 5-9 Alarm delay
The alarm name, delay time, delay enabling and alarm type are displayed from left to right in the list.
The alarm delay can be set to 0 ~ 9999. Unit: second.
Liebert.PEX2 Series Air Conditioner User Manual