68 Chapter 6 Battery
NX UPS Single Module And Parallel System 250kVA ~ 800kVA User Manual
1
2
3
4
W812
W811
C2 board
W813
W802
W809
W810
Note 1: Current leakage protective device
is optional. The positive, negative and
neutral battery cables should be routed
through the sensor, but the earth cable
should not be routed through the sensor.
X107
X108
X103
X104
X106
X105
X100
X101
X101
X107 X100
X102
X102
X103
X104
X106
X105
X108
J1
J2
J4
J7
J3
J5
J6
X812
X8
:
J15
X8
:
J32
W801
J1
W802
J2
W809
W810
PE
N
+
-
Note 2: The communication cable W811
of battery temperature sensor can only be
connected to the J32 port of control
module of bypass cabinet, the ports J31,
J30 and J29 are invalid to temperature
detection.
IN-
IN-N
Battery temperature sensor (0 ~ 4 pcs)
Connect to ports J15, J19, J20
and 21 of control module of
bypass cabinet as illustrated
Connect to ports J32, J31, J30
and 29 of control module of
bypass cabinet as illustrated
PCB of battery ground
fault detector (M5 board)
PCB of battery ground
fault detector (C15 board)
C2 board
Figure 6-5 Connection diagram of BCB box
6.10 Battery Temperature Sensor (Option)
Emerson provides an optional battery temperature sensor. Conect the battery temperature sensor as shown in
Figure 6-5.
6.11 Battery Ground Fault Detector (Option)
Emerson provides an optional battery ground fault detector. It includes a current transformer and a PCB, which
should be installed in the BCB box. The installation position of the PCB is shown in Figure 6-4. If the BCB box uses
top cable entry, the current transformer should be installed on the inside of the top plate of the BCB box, as shown in
Figure 6-4; if the BCB box uses bottom cable entry, the current transformer should be installed on the inside of the
bottom plate of the BCB box. Connect the PCB as shown in Figure 6-5.
Note
If a battery ground fault detector is installed, the positive, negative and neutral battery cables from the battery into the BCB box
must be routed through the hole of the current transformer of the battery ground fault detector, while other cables must bypass the
current transformer.