Installation Drawings
Liebert
®
e
XL
™
18
Figure 6
Outline Drawing, 625-800kVA Liebert
e
XL single-module UPS
Notes
1. 24" (610mm) minimum clearance above unit required for air exhaust,
and 36" (914mm) front access required for service.
2. Keep cabinet within 15 degrees of vertical while handling.
3. Top and bottom cable entry available through removable
access plates. Remove punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. All wiring is to be in accordance with national and local electrical codes.
7. Width dimension includes side panels. Subtract 1.4" (35mm)
when removing both side panels.
8. See technical information drawing for shipping split weights.
To Frame
2.6" (65mm)
To
Frame
1.3"
(33mm)
U46-8C-2001
Rev. 3
RIGHT SIDE VIEW
33.5"
(851mm)
34.4"
(874mm)
77.5"
(1969mm)
With Accent Strip
See
Bottom
View
38.5"
(978mm)
51.2"
(1300mm)
123.6" (3140mm)
33.9"
(862mm)
To Frame
2.4" (60mm)
4" (101mm)
to Frame
Rectifier\DC
Cable Entry, Area
With Panel Removed
12.5" x 21.9"
(318mm x 556mm)
Rectifier\DC
Cable Entry, Area
With Panel Removed
(23.5" x 21.8"
(597mm) x 553mm)
Panel to Frame
Typical
Opposite
Side
To Frame
1.3" (33mm)
14.3" (363mm)
to Frame
To Frame Typ
Opposite Side
1.6" (40mm)
Low-Voltage Cable
Entry\Exit, Area
With Panel Removed
4.9" x 21.8" (125mm x 553mm)
Bypass\ Output
Cable Exit, Area
With Panel Removed
10.9" x 28.4" (278mm x 722mm)
1.4" (37mm)
Section A - (Top Looking Down)
BOTTOM VIEW
Input
Core
Core
Output/Bypass
TOP VIEW
FRONT VIEW
Low Voltage Cable
Entry \ Exit, Area
With Panel Removed
8.8" x 9.8"
(224mm x 250mm)
Bypass\Output
Cable Exit, Area
With Panel Removed
12.5" x 23.2"
(318mm x 590mm)