Installation Drawings
21
Liebert
®
e
XL
™
Figure 11 Low-voltage cable routing
Use these entry holes for
Liebert IntelliSlot
®
Unity
™
card cables only
Use these entry holes for
Liebert IntelliSlot
®
Unity
™
card cables only
DOORS AND INNER SKINS REMOVED
INPUT
Low Voltage
Control Cable
Top Entry
Low Voltage
Wire Way
Low-Voltage
Control Cable
Bottom Entry
Provide at least 18" (457mm) of service loop
to all control connections to permit opening
the service drawer without removing the connections.
The extra service loop can either be left hanging
or loosely attached to the corner post.
Service Drawer
Openings to Control Wire Way
To Ensure Isolation:
All wiring must have insulation rated
for 600V or higher.
• All cables not rated Class 1 must be
kept separated and secured away
from high-voltage Class 1 cables.