MANUAL SETUP
OPTIONS TAB
MODE
WRITE ALARM
CONFIGURE
RESOURCE BLOCK
TRANSDUCER BLOCK
ALERT KEY
MAXIMUM ALERTS ALLOWED
MAXIMUM ALERTS POSSIBLE
FEATURES SELECTED
BOCK ALARM
WRITE LOCK
CONFIRM TIME
COMMUNICATION TIMEOUT
FUNCTION
BLOCK AVAILABLE
Figure 16. Configure > Manual Setup > Options
Alarm State—
indicates the state of the Write Alarm. Five states are possible; Undefined, Clear‐Reported, Clear-Not
Reported, Active‐Reported, Active‐Not Reported.
Unacknowledged
—select Undefined, Acknowledged, or Unacknowledged
Block Alarm
The block alarm is used for all configuration, hardware, connection failure, or system problems in the block. Alarm
Summary (ALARM_SUM [37]) determines if the Write Alarm and Block Alarm are disabled.
Block Alarm Disabled—
select to disable the Block Alarm
Alarm State—
indicates the state of the Block Alarm. Five states are possible; Undefined, Clear‐Reported, Clear-Not
Reported, Active‐Reported, Active‐Not Reported.
Unacknowledged—
select Undefined, Acknowledged, or Unacknowledged
Write Lock
Write Lock determines if writes are permissible to other device parameters.
Write Lock
— When Write Lock is set to Locked, no writes are permitted to any parameters within the device except to
set Write Lock to Not Locked. When locked, the device functions normally, updating inputs and outputs and executing
algorithms. When Write Lock is set to Not Locked, the Write Alarm alert is active.
Write Priority
—Write Priority sets the priority for Write Alarm. The lowest priority is 0. The highest is 15.