Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
April 2022
23
Confirm Time
Confirm Time determines the time in 1/32 of a millisecond, the instrument waits for confirmation of receipt of a report
before trying again. If Confirm Time is 0, the instrument does not try to resend the report. Enter 0 or a value between
320000 (10 seconds) and 640000 (20 seconds).
Communication Timeout
Rcas Time‐Out
—Rcas Timeout determines how long function blocks in the DLC3020f should wait before giving up on
remote computer writes to RCas parameters. When the timeout is exceeded, the block sheds to the next mode as
defined by the block shed options. If RCas Timeout is set to 0, the block will not shed from RCas. Enter a positive value
in the RCas Timeout Timeout field. Time duration is in 1/32 milliseconds (640000 = 20 secs).
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your “advanced” control.
Default value for RCas Timeout is 20 seconds.
Rout Time-Out
—ROut Timeout (SHED_ROUT [27]) determine how long function blocks in the DLC3020f should wait
before giving up on computer writes to ROut parameters. When the timeout is exceeded, the block sheds to the next
mode as defined by the block shed options. If ROut Timeout is set to 0, the block will not shed from ROut. Enter a
positive value in the ROut Timeout field. Time duration is in 1/32 milliseconds (640000 = 20 secs).
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your “advanced” control.
Default value for ROut Timeout is 20 seconds.
Write Lock
—permits using Write Lock to prevent any external change to parameter values. Block connections and
calculation results will proceed normally, but the configuration is locked.
Reannunciation
—permits the instrument to support Reannunciation of alarms.
Function Block Available
CasIn to Transducer Block