Quick Start Guide
D103470X012
DLC3020f Digital Level Controller
April 2022
15
CONFIGURE
MANUAL SETUP
DEVICE TAB
SELECT UNIT SYSTEM
SENSOR PARAMETERS
VARIABLE
CONFIGURATION
SENSOR LIMITS
INSTRUMENT
MOUNT POSITION
TORQUE TUBE
SENSOR HARDWARE
INFORMATION
Figure 11. Configure > Manual Setup > Device
Primary Value Offset—
the constant offset applied to the level/interface measurement.
Primary Value Range Units—
units for PV, PV Range, and Sensor Limits.
Sensor Limits
Upper Sensor Limit—
Indicates the maximum usable value for the Primary Value Range High.
Lower Sensor Limit—
Indicates the minimum usable value for the Primary Value Range Low.
The Upper and Lower Sensor Limit limit what the DLC3020f can read; values above and below these limits will not be
detected by the instrument. This is a dynamic reading based on temperature used when Temperature Compensation
is enabled.
Sensor Hardware Information
Enter the following information by selecting
Sensor Hardware Information.
Model Type, End Connection Style, End Connection Type, Body Material, Pressure Rating, Mechanical Sensor Serial
Number, Displacer Size Displacer Material, Displacer Rating, G Dimension, Torque Tube Material, Torque Tube Wall,
Heat Insulator.
Sensor information is typically found on the sensor nameplate.
Note
This data is informational only and is not used in calibration or PV calculations.