Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

  

Date: 17.12.2020

 

Am Borsigturm 31 I 13507 Berlin I Germany 

 

EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx 

G e n e r a l   i n fo r ma t i o n : 

EXD-HP1/2 are stand-alone superheat and or economizer controllers. EXD-HP1 is 

intended for operation of one EXM/EXL  or  EXN  valve whereas EXD-HP2 is 

designed for operation of two independent EXM/EXL or two EXN valves.  

Note: It is possible to use only circuit 1 from EXD-HP2. In this case, the circuit 

2 must be disabled (C2 parameter) and the sensors and the valve for the second 

circuit are not needed.  

ModBus communication is described in a Technical Bulletin and it is not covered 

by this document. 
T e c h ni c a l   D a ta :  

Power supply 

24VAC/DC ±10%; 1A 

Power consumption 

EXD-HP1: 15VA          EXD-HP2: 20VA 

Plug-in connector 

Removable screw terminals wire size 0.14...1.5 mm

2

 

Protection class 

IP20 

Digital Inputs 

Potential free contacts (free from voltage) 

Temperature sensors 

ECP-P30 

Pressure sensors 

PT5N 

Operating/surrounding temp.  0…+55°C 

Output alarm relay 

SPDT contact 24V AC 1 Amp inductive load; 

24V AC/DC 4 Amp resistive load 

Activated/energized: During normal operation (no alarm condition) 

Deactivated/de-energized: During alarm condition or power supply is OFF 

Stepper motor output 

Coil: EXM-125/EXL-125 or EXN-125 

Valves: EXM/EXL-… or EXN-… 

Type of action 

1B 

Rated impulse voltage 

0.5kV 

Pollution Degree 

Mounting:  

For standard DIN rail 

Marking 

   

 

Dimensions (mm)

 

 

Warning -Flammable refrigerants: 

 

EXD-HP1/2 has a potential ignition source and does not comply with ATEX 

requirements. Installation only in non-explosive environment. For flammable 

refrigerants only use valves and accessories approved for it!

 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure to comply can result in device 

failure, system damage or personal injury. 

 

It is intended for use by persons having the appropriate knowledge and skill. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Do not apply voltage to the controller before completion of wiring. 

 

Entire electrical connections have to comply with local regulations. 

 

Inputs are not isolated, potential free contacts needed to be used. 

 

Disposal: Electrical and electronic waste must NOT be disposed of with other 

commercial waste. Instead, it is the user responsibility to pass it to a designated 

collection point for the safe recycling of Waste Electrical and Electronic 

Equipment (WEEE directive 2019/19/EU). For further information, contact 

your local environmental recycling center. 

E l e c t r i c a l   c o n ne c t i o n   a n d   w i r i ng : 

•  Refer to the electrical wiring diagram for electrical connections. 

•  Note: Keep controller and sensor wiring well separated from supply power 

cables. Minimum recommended distance 30mm. 

• 

EXM-125, EXL-125 or EXN-125 coils are supplied with fix cable and JST terminal 

block at cable end. Cut the wires close to terminal block. Remove the wire 

insulation approximately 7 mm at the end. It is recommended that the wires end to  

be equipped with core cable ends or metallic protective sleeve. 

When connecting 

the wires of EXM/EXL or EXN, consider the color coding as follows: 

EXD 

Terminal 

EXM/L-125 wire color  EXN-125 wire color 

EXD-HP1 

6  

BR 

7  

BL 

8  

OR 

9  

YE 

10 

WH

 

Brown 

Blue 

Orange 

Yellow 

White 

Red 

Blue 

Orange 

Yellow 

White 

EXD-HP2 

30 

BR 

31 

BL 

32 

OR 

33 

YE 

34 

WH

 

Brown 

Blue 

Orange 

Yellow 

White 

Red 

Blue 

Orange 

Yellow 

White 

 

The  digital input DI1 (EXD-HP1) and DI1/D12 (EXD-HP1/2) are the 

interfaces between EXD-HP1/2 and upper level system controller if the 

Modbus communication has not been used. The external digital shall be 

operated in function system’s compressor/demand.

  

 

If the output relays are not utilized, the user must ensure appropriate safety 

precautions are in place to protect the system. 

Operating condition 

Digital input status 

Compressor starts/run 

closed (Start)  

Compressor stops 

open (Stop) 

Note:  Connecting any EXD-HP1/2 inputs to the supply voltage will 

permanently damage the EXD-HP1/2. 

W i r i n g   b a se   bo a r d   ( E X D -H P 1 / 2 ) : 

 

 

Note:  

 

Base board is for function of superheat control or Economizer control. 

 

Alarm relay, dry contact. Relay coil is not energized during alarm condition or 

power off. 

 

Hot gas discharge sensor input is mandatory only for economizer control function. 

Warning: Use a class II category transformer for 24VAC power supply. Do 

not ground the 24VAC lines. We recommend using individual transformers for 

EXD-HP1/2 controller and for third party controllers to avoid possible 

interference or grounding problems in the power supply. 

  

 

Summary of Contents for EXD-HP1

Page 1: ... to comply with local regulations Inputs are not isolated potential free contacts needed to be used Disposal Electrical and electronic waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2019 19 EU For further information contact...

Page 2: ...selected parameter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TI...

Page 3: ... 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant 1u0 The default value can be changed see MOP table Code Parameter description and choices Min Max Factory setting 1P9 Low pressure alarm mode circuit 1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit 1 0 8 17 7 0 1Pb Low pressure...

Page 4: ...edure Do wnl oa di ng pr oc e dure configured parameters from key to other controllers Turn off power to new controller Insert a loaded Key with stored data from reference controller into new controller and turn on the power supply The stored parameters of the key will be downloaded automatically into the new controller memory The doL message appears followed by a End message for 5 seconds The new...

Page 5: ...rbindungen vollständig sind Die Anlage darf erst dann in Betrieb genommen werden wenn alle Verbindungen hergestellt sind Für den gesamten elektrischen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattd...

Page 6: ...ind passwortgeschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert d...

Page 7: ... 2 PT5N 30 3 PT5N 10P FLR 1uu Ventilöffnungsgrad bei Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 Code Parameter Beschreibung und Auswahl Min Max Werk 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL 1 2 Rückstell autom manuell wenn 1uL 0 Rückstellu...

Page 8: ...erden Ko nfig ura tio nspar am e ter a uf de n Ko pie r sc hl üsse l lade n Der Referenz Regler muss eingeschaltet sein Kopierschlüssel einstecken und Taste betätigen Auf der Anzeige erscheint die Meldung uPL danach 5 Sekunden lang End Hinweis Falls die Fehlermeldung Err angezeigt wird Prozedur wiederholen Ko nfig ura tio nspar am e ter v om Ko pie r sc hl üssel a uf ande r e Re g le r übe r trag ...

Page 9: ...ия Не подавайте питание на контроллер до окончания монтажа Проводите электрические подключения в соответствии с местными стандартами Входы не изолированы используйте сухие контакты Утилизация Электронные и электрические отходы НЕ ДОЛЖНЫ утилизироваться вместе с другими коммерческими отходами Обязанность пользователя передать их в предназначенное место для безопасной переработки электрического и эл...

Page 10: ...етра Нажимайте или ля увеличения уменьшения значения параметра Нажмите для подтверждения нового значения Повторите процедуру от нажмите или для выбора Выход и сохранение новых значений Нажмите для подтверждения новых значений и покиньте процедуру изменения параметров Выход без сохранения Не нажимайте ничего в течение по крайней мере 60 секунд TIME OUT Возврат всех параметров к заводским настройкам...

Page 11: ...испарителя 1 разрешён автовозврат 2 разрешён ручной возврат 1u5 Уставка перегрева K если 1uL 1 или 2 если 1uL 0 3 0 5 30 30 6 6 1u2 Функция MOP 0 1 1 0 запрещён 1 enable 1u3 Температура насыщения MOP Контур 1 C См таблицу MOP Заводская настройка соответствует выбранному хладагенту 1u0 и может быть изменена Код Описание параметра и возможности выбора Мин Макс Заводская настройка 1P9 Режим работы ав...

Page 12: ...во включенный контроллер и нажмите кнопку появится сообщение uPL а затем через 5 сек сообщение End Внимание Появление сообщения Err означает сбой записи Повторите вышеописанную процедуру В ыгру зк а записьсконфигурированныхпараметровсключанадругиеконтроллеры Выключите питание нового котроллера Вставьте ключ с параметрами в новый контроллер и включите его питание Параметры с ключа автоматически выг...

Reviews: