Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

  

Date: 17.12.2020

 

Am Borsigturm 31 I 13507 Berlin I Germany 

 

EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx 

W i r i n g :   U p p e r   bo a r d   ( E XD - H P 2 ) :  

 

 

Note:  

 

Upper board is only for function of superheat control. 

 

Upper board does not need to be wired if the circuit 2 is disabled. 

 

P r e pa r a t i o n   f o r   S ta r t - u p :  

 

Vacuum the entire refrigeration circuit. 

 

  Warning:  Electrical Control Valves EXM/EXL or  EXN are delivered 

partially open position. Do not charge system with refrigerant before closure 

of valve. 

 

Apply supply voltage 24V to EXD-HP1/2 while the digital input (DI1/DI2) is 

OFF(open). The valve will be driven to close position. 

 

After closure of valve, start to charge the system with refrigerant. 

S e t u p   o f   pa r a me t e r s : 

(need to be checked/modified before start-up) 

 

Make sure that digital input (DI1/DI2) is off (open). Turn the power supply ON. 

 

Four main parameters Password (H5), type of function (1uE), refrigerant type 

(1u0/2u0) and pressure sensor type (1uP/2uP) can be set only when digital input 

DI1/DI2 is off (open) while the power supply is ON (24V). This feature is for added 

safety to prevent accidental damage of compressors and other system components. 

 

Once the main parameters have been selected/saved the EXD-HP1/2 is ready for 

startup. All other parameters can be modified at any time during operation or 

standby if it is necessary. 

D i s p l a y / k e y p a d   u ni t   ( L E Ds   a n d   b u t t o n  f u n c t i o n s ) :  

 

 

 

          

 

 

 

 

 

 
P r o c e d u r e   fo r   pa r a me t e r   m o di f i c a t i o n : 

The parameters can be accessed via the 4-button keypad. The configuration 

parameters are protected by a numerical password. The default password is “12”. To 

select the parameter configuration: 

 

Press the 

 button for more than 5 seconds, A flashing “0” is displayed 

 

Press 

 until “12” is displayed; (password) 

 

Press 

 to confirm password 

 

Press 

or 

 to show the code of the parameter that has to be changed 

 

Press

 

 to display the selected parameter value 

 

Press 

or 

 to increase or decrease the value 

 

Press 

 to temporarily confirm the new value and display its code 

 

Repeat the procedure from the beginning "press 

or 

 to show..." 

To exit and save the new settings

 

Press 

  to confirm the new values and exit the parameters modification 

procedure. 

To exit without modifying/saving any parameters:

  

 

Do not press any button for at least 60 seconds (TIME OUT). 

Reset all parameters to factory setting: 

 

Make sure that digital input (DI1/DI2) is Off (open). 

 

Press 

 and 

 together for more than 5 seconds. 

 

A flashing “0” is displayed. 

 

Press 

or 

 until the password is displayed (Factory setting = 12).  

 

If password was changed, select the new password. 

 

Press 

 to confirm password 

 

Factory setting are applied 

Note: In standard mode the actual superheat is shown at the display. In case of liquid 

injection and economizer function this change to discharge temperature. 

 

To display other data of circuit 1 of EXD-HP1/2 or 2 of EXD-HP2:  

– 

Press 

 and 

 together for 3 seconds to show data of circuit 1 

– 

Press 

 and 

 together for 3 seconds to show data of circuit 2 

 

To display data of each circuit: Press the 

  button for 1 second until index 

number according to the below table appears. Release the 

 

button and the next 

variable data will appear. By repeating above procedure, variable data can be 

displayed in a sequence as Measured superheat (K) → Measured sucti

on pressure 

(bar)  →  Valve  position  (%)

 

→  Measured  suction  gas  temperature  (°C)  → 

Calculated saturated temperature (°C) 

→ Measured discharge temperature (°C) (if 

economizer function is selected) 

→REPEATING….

 

Variable data 

Circuit 1 (EXD-HP1/2) 

Circuit 2 (EXD-HP2) 

Default Superheat K 

1                 0 

2                 0 

Suction pressure bar 

1                 1 

2                 1 

Valve position % 

1                 2 

2                 2 

Suction gas temp °C. 

1                 3 

2                 3 

Saturation temp. °C 

1                 4 

2                 4 

Discharge temp. °C 

1                 5 

-

 

Note 1: Discharge temp. is available only if economizer function is selected. 

Note 2: After 30 minutes, display reverts to index 0.

Blinking:

 valve is closing 

ON:

 valve is fully close 

Blinking:

 valve is opening 

ON:

 valve is fully open 

ON

: alarm 

OFF: no alarm 

Parameters setting/saving 

Selecting/ 

confirming 

Next parameter/ 

value (higher) 

Next parameter/ 

value (lower) 

ON

: Data display 

Circuit 1 

ON

: ModBus 

communication 

ON

: Data display 

Circuit 2 

Summary of Contents for EXD-HP1

Page 1: ... to comply with local regulations Inputs are not isolated potential free contacts needed to be used Disposal Electrical and electronic waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2019 19 EU For further information contact...

Page 2: ...selected parameter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TI...

Page 3: ... 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant 1u0 The default value can be changed see MOP table Code Parameter description and choices Min Max Factory setting 1P9 Low pressure alarm mode circuit 1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit 1 0 8 17 7 0 1Pb Low pressure...

Page 4: ...edure Do wnl oa di ng pr oc e dure configured parameters from key to other controllers Turn off power to new controller Insert a loaded Key with stored data from reference controller into new controller and turn on the power supply The stored parameters of the key will be downloaded automatically into the new controller memory The doL message appears followed by a End message for 5 seconds The new...

Page 5: ...rbindungen vollständig sind Die Anlage darf erst dann in Betrieb genommen werden wenn alle Verbindungen hergestellt sind Für den gesamten elektrischen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattd...

Page 6: ...ind passwortgeschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert d...

Page 7: ... 2 PT5N 30 3 PT5N 10P FLR 1uu Ventilöffnungsgrad bei Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 Code Parameter Beschreibung und Auswahl Min Max Werk 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL 1 2 Rückstell autom manuell wenn 1uL 0 Rückstellu...

Page 8: ...erden Ko nfig ura tio nspar am e ter a uf de n Ko pie r sc hl üsse l lade n Der Referenz Regler muss eingeschaltet sein Kopierschlüssel einstecken und Taste betätigen Auf der Anzeige erscheint die Meldung uPL danach 5 Sekunden lang End Hinweis Falls die Fehlermeldung Err angezeigt wird Prozedur wiederholen Ko nfig ura tio nspar am e ter v om Ko pie r sc hl üssel a uf ande r e Re g le r übe r trag ...

Page 9: ...ия Не подавайте питание на контроллер до окончания монтажа Проводите электрические подключения в соответствии с местными стандартами Входы не изолированы используйте сухие контакты Утилизация Электронные и электрические отходы НЕ ДОЛЖНЫ утилизироваться вместе с другими коммерческими отходами Обязанность пользователя передать их в предназначенное место для безопасной переработки электрического и эл...

Page 10: ...етра Нажимайте или ля увеличения уменьшения значения параметра Нажмите для подтверждения нового значения Повторите процедуру от нажмите или для выбора Выход и сохранение новых значений Нажмите для подтверждения новых значений и покиньте процедуру изменения параметров Выход без сохранения Не нажимайте ничего в течение по крайней мере 60 секунд TIME OUT Возврат всех параметров к заводским настройкам...

Page 11: ...испарителя 1 разрешён автовозврат 2 разрешён ручной возврат 1u5 Уставка перегрева K если 1uL 1 или 2 если 1uL 0 3 0 5 30 30 6 6 1u2 Функция MOP 0 1 1 0 запрещён 1 enable 1u3 Температура насыщения MOP Контур 1 C См таблицу MOP Заводская настройка соответствует выбранному хладагенту 1u0 и может быть изменена Код Описание параметра и возможности выбора Мин Макс Заводская настройка 1P9 Режим работы ав...

Page 12: ...во включенный контроллер и нажмите кнопку появится сообщение uPL а затем через 5 сек сообщение End Внимание Появление сообщения Err означает сбой записи Повторите вышеописанную процедуру В ыгру зк а записьсконфигурированныхпараметровсключанадругиеконтроллеры Выключите питание нового котроллера Вставьте ключ с параметрами в новый контроллер и включите его питание Параметры с ключа автоматически выг...

Reviews: