32
Factory-Set Control Terminal Functions
I/O Connection
External Wiring Pin
Signal Name Signal
Default Setting
Description
1
+10V
Ref. Output Voltage
-
10VDC Supply Source
2
AI1+
a
Analog Input 1
0-10V
Voltage Speed Reference (Programmable to 4-20mA)
3
AI1-
Analog Input 1 Ground
-
Analog Input 1 Common (Ground)
4
AI2+
a
Analog Input 2
4-20mA
Current Speed Reference (Programmable to 0-10V)
5
AI2-
Analog Input 2 Ground
-
Analog Input 2 Common (Ground)
6
GND
I/O Signal Ground
-
I/O Ground for Reference and Control
7
DIN5
Digital Input 5
Preset Speed B0
Sets frequency output to Preset Speed 1
8
DIN6
Digital Input 6
Fire Mode
Enables drive into Fire Mode
9
DIN7
Digital Input 7\TI+
Bypass Start
Enables drive into Bypass mode waiting for drive start
10
DIN8
Digital Input 8\TI-
Force Auto
Input forces drive into Auto Control place
11
CMB
DI5 to DI8 Common
Grounded
Allows source input
12
GND
I/O Signal Ground
-
I/O Ground for Reference and Control
13
24Vo
+24VDC Output
-
Control voltage output (100mA Max)
14
DO1
Digital Output 1
Ready
Shows the drive is ready to run
15
24Vo
+24VDC Output
-
Control voltage output (100mA Max)
16
GND
I/O Signal Ground
-
I/O Ground for Reference and Control
17
AO1+
Analog Output 1
Output Frequency
Shows Output frequency to motor 0 - 60Hz (4-20mA)
18
AO2+
Analog Output 2
Motor Current
Shows Motor current of motor 0-FLA (4-20mA)
19
24Vi
+24VDC Input
-
External control voltage input
20
DIN1
Digital Input 1
Run Forward
Input starts drive in forward direction (start enable)
21
DIN2
Digital Input 2
Run Reverse
Input starts drive in reverse direction(start enable)
22
DIN3
Digital Input 3
External Fault
Input causes drive to fault
23
DIN4
Digital Input 4
Fault Reset
Input resets active faults
24
CMA
DI1 to DI4 Common
Grounded
Allows source input
25
A
RS-485 Signal A/+
-
Fieldbus Communication (Modbus, BACnet)
26
B
RS-485 Signal B/-
-
Fieldbus Communication (Modbus, BACnet)
27
R3NO
Relay 3 Normally Open
Fault
Relay output 3 shows VFD is Faulted
28
R1NC
Relay 1 Normally Closed
Bypass Run
Relay output 1 shows VFD is in a bypass run state
29
R1CM
Relay 1 Common
30
R1NO
Relay 1 Normally Open
31
R3CM
Relay 3 Common
Fault
Relay output 3 shows VFD is Faulted
32
R2NC
Relay 2 Normally Closed
Run
Relay output 2 shows VFD is in a drive run state
33
R2CM
Relay 2 Common
34
R2NO
Relay 2 Normally Open
Notes
-
The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to
ground (as shown by dashed line). If a SOURCE configuration is desired, wire 24 V to CMA and CMB
and close the inputs to ground. When using the +10 V for AI1, it is important to wire AI1—to ground (as
shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered
together.
-
AI1+ and AI2+ block that it can support 10K potentiometer.
i
Re
s
Summary of Contents for EVH Series
Page 1: ...Copeland Commercial HVACR Variable Frequency Drive EVH Series Installation Manual ...
Page 5: ...5 Rating Label Carton Label Keypad Button Overview ...
Page 13: ...13 Rubber Grommet Installation Instructions Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 ...
Page 31: ...31 Step 3 Control Board Layout ...
Page 37: ...37 H1 H1S Approximate dimensions in inches mm ...
Page 38: ...38 H2 H2S Approximate dimensions in inches mm ...
Page 39: ...39 H3 H3X IP54 Approximate dimensions in inches mm ...
Page 40: ...40 H4 CX IP54 Approximate dimensions in inches mm ...
Page 41: ...41 DX IP21 DX IP54 Approximate dimensions in inches mm ...
Page 44: ...44 ...
Page 45: ...45 ...